| Plan Review Notes For Permit 17020292 |
| Permit Number |
17020292 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-02-09 13:57:38 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014) | | | | | | 1- FLAT ROOF NOA 14-1030.02 SUBMITTED; | | | A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO | | | BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN | | | PRESSURES REQUIRED BY SEC. R301.1 FBC-RESIDENTIAL, 5TH | | | EDITION (2014). | | | | | | B) IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | | PRESSURES REQUIRED BY SEC. R301.1 FBC-RESIDENTIAL FOR | | | ALL ROOF ZONES, THEN NEED TO PROVIDE SIGNED AND SEALED | | | RAS 117 CALCULATIONS AS REQUIRED BY GENERAL LIMITATION | | | #7 ON LAST PAGE OF NOA SUBMITTED. | | | NOTE: ASSEMBLIES WITH GENERAL LIMITATION #9 CAN NO BE | | | USED IF THE DESIGN PRESSURES ARE TOO LOW. GENERAL | | | LIMITATION $9 DOESN'T ALLOW RAS 117 CALCULATIONS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|