| Notes |
| Date |
Text |
| 2017-02-13 15:59:08 | RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW | | | CHECKLIST. | | | CODE: FBC 5TH EDITION (2014) | | | | | | 1- NEW FLAT ROOF FLORIDA PRODUCT APPROVAL FL1654-R19 | | | SUBMITTED: | | | SELECTED ASSEMBLY W52 DOESN'T MEET THE DESIGN PRESSURES | | | FOR ALL ROOF ZONES. PROVIDE SIGNED AND SEALED RAS 117 | | | CALCULATIONS (2 COPIES) AS REQUIRED BY NOTE #11 TO MEET | | | THE DESIGN PRESSURES REQUIRED BY SEC. R301.1 | | | FBC-RESIDENTIAL FOR THE CORNER AREAS. | | | | | | NOTE: THERE ARE TWO DIFFERENT TYPES OF ROOF PROPOSED | | | FOR THIS PROJECT. THERE IS ONE INSULATED ROOF SYSTEM | | | (W-52) AND ONE NON-INSULATED ROOF SYSTEM (W-106). THE | | | INSULATED ROOF SYSTEM NEEDS THE RAS 117 CALCULATIONS TO | | | MEET THE DESIGN PRESSURES FOR ROOF ZONE #3. ACCORDING | | | TO TABLE R301.2(2) -RESIDENTIAL THE CORNER PRESSURES | | | FOR CORNER AREA FOR A ONE STORY BUILDING IS -95.7PSF. | | | THE NON-INSULATED ROOF SYSTEM (W-106) IS OK BECAUSE THE | | | DESIGN PRESSURES ARE HIGH ENOUGH TO COVER ALL ROOF | | | ZONES. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|