| Plan Review Notes For Permit 17020285 |
| Permit Number |
17020285 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-02-09 11:01:45 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014) | | | | | | 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL16717-R3 | | | SUBMITTED: | | | SELECTED ASSEMBLIES W43 AND W-88 DON'T MEET THE DESIGN | | | PRESSURES FOR ALL ROOF ZONES. PROVIDE SIGNED AND SEALED | | | RAS 117 CALCULATIONS (2 COPIES) AS REQUIRED BY NOTE #11 | | | TO MEET THE DESIGN PRESSURES REQUIRED BY SEC. R301.1 | | | FBC-RESIDENTIAL FOR PERIMETER AND CORNER AREAS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|