| Plan Review Notes For Permit 17020283 |
| Permit Number |
17020283 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-23 10:50:29 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO SETS OF PRODUCT APPROVALS, THAT HAVE BEEN | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD, FOR THE GREENHECK EXHAUST FAN THAT SHOW IT | | | MEETS REQUIRED WIND DESIGN PRESSURES. FBC 107.3.4.1 | | | | | | 2) SHOW COMPLIANCE WITH FBCR-M1506.2 M1506.2 EXHAUST | | | OPENINGS. AIR EXHAUST OPENINGS SHALL TERMINATE NOT LESS | | | THAN 3 FEET (914 MM) FROM PROPERTY LINES; 3 FEET (914 | | | MM) FROM OPERABLE AND NONOPERABLE OPENINGS INTO THE | | | BUILDING AND 10 FEET (3048 MM) FROM MECHANICAL AIR | | | INTAKES EXCEPT WHERE THE OPENING IS LOCATED 3 FEET (914 | | | MM) ABOVE THE AIR INTAKE. OPENINGS SHALL COMPLY WITH | | | SECTIONS R303.5.2 AND R303.6. | | | |
|