| 2017-03-08 08:33:29 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA RES BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. PLEASE LABEL GARAGE DOOR OPENER RECEPTACLES TO BE | | | GFCI PROTECTED PER FBC RES E3902.2. READILY ACCESSIBLE. | | | 2. CLARIFY AS LOADS FOR THE CAR LIFT AND STORAGE LIFT | | | ARE NOT SHOWN ON CALCULATED PANEL LOADS. | | | 3. GENERAL NOTE TO INDICATE REQUIRED SEPARATE PERMIT | | | FOR GENERATOR INSTALLATION. A COMPLETE ELECTRICAL | | | GENERATOR PACKAGE WILL NEED TO BE SUBMITTED AT THAT | | | TIME. FBC 107.3.5 | | | 4. PROVIDE A NOTE TO SHOW REQUIRED TAMPER RESISTANT | | | RECEPTACLES PER FBC RES E4002.14 | | | 5. PLEASE CLARIFY THE ATS SHOWN ON GARAGE WALL, AS | | | RISER INDICATES DIFFERENT LOCATION AT CABANA. IS THIS | | | THE PROPOSED LOCATION FOR THE PARALLELING GENERATOR | | | EQUIPMENT? IF SO LABEL ACCORDINGLY. | | | 6. ZONING COMMENTS WILL NEED TO BE ADDRESSED PRIOR TO | | | AN ELECTRICAL APPROVAL. | | | 7. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | | QUESTIONS OR CONCERNS. | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | |
|