| 2017-04-27 13:47:34 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17020277 | | | 4/27/17 | | | | | | 1) M-4: THE O/A CALCULATIONS FOR THE FELLOWSHIP AREA- | | | AHU'S- 8A & 8B INDICATE DEMAND CONTROLLED VENTILATION | | | IS REQUIRED- SECTION C403.2.5.1 FBC-14 ENERGY | | | CONSERVATION. | | | | | | 2) M-4: THE O/A CALCULATIONS FOR THE CHOIR/PLATFORM ARE | | | NOT IN COMPLIANCE WITH TABLE 403.3 WHICH REQUIRES AN | | | O/A RATE BASED ON 70 PERSONS PER 1000 SF. | | | | | | 3) PROVIDE MAKE-UP AIR FOR EF-1 IN THE WARMING KITCHEN- | | | SECTION 508.1. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|