Plan Review Notes
Plan Review Notes For Permit 17020277
Permit Number 17020277
Review Stop M
Sequence Number 2
Notes
Date Text
2017-04-27 13:47:342ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17020277
 4/27/17
  
 1) M-4: THE O/A CALCULATIONS FOR THE FELLOWSHIP AREA-
 AHU'S- 8A & 8B INDICATE DEMAND CONTROLLED VENTILATION
 IS REQUIRED- SECTION C403.2.5.1 FBC-14 ENERGY
 CONSERVATION.
  
 2) M-4: THE O/A CALCULATIONS FOR THE CHOIR/PLATFORM ARE
 NOT IN COMPLIANCE WITH TABLE 403.3 WHICH REQUIRES AN
 O/A RATE BASED ON 70 PERSONS PER 1000 SF.
  
 3) PROVIDE MAKE-UP AIR FOR EF-1 IN THE WARMING KITCHEN-
 SECTION 508.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER