Plan Review Notes
Plan Review Notes For Permit 17020277
Permit Number 17020277
Review Stop P
Sequence Number 1
Notes
Date Text
2017-02-17 14:02:061ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. A GREASE INTERCEPTOR WILL BE REQUIRED FOR THE 3 COMP
 SINK, S1 AND THE DISHWASHERS. PER FBC PL 1003.1 +
 1003.3.1
  
 2. THE GARBAGE DISPOSALS SHALL COMPLY WITH FBC PL
 1003.3.2 FOOD WASTE GRINDERS.
 WHERE FOOD WASTE GRINDERS CONNECT TO GREASE
 INTERCEPTORS, A SOLIDS INTERCEPTOR SHALL SEPARATE THE
 DISCHARGE BEFORE CONNECTING TO THE GREASE INTERCEPTOR.
 SOLIDS INTERCEPTORS AND GREASE INTERCEPTORS SHALL BE
 SIZED AND RATED FOR THE DISCHARGE OF THE FOOD WASTE
 GRINDER. EMULSIFIERS, CHEMICALS, ENZYMES AND BACTERIA
 SHALL NOT DISCHARGE INTO THE FOOD WASTE GRINDER.
  
 3. THE REVENT ON S1 IS NOT ALLOWED IT SHALL COMPLY WITH
 FBC PL 904.3 VENT TERMINATION.
 VENT STACKS OR STACK VENTS SHALL TERMINATE OUTDOORS TO
 THE OPEN AIR OR TO A STACK-TYPE AIR ADMITTANCE VALVE IN
 ACCORDANCE WITH SECTION 918.
  
 4. THE DISHWASHER CAN NOT CONNECT SEPARATELY TO
 DRAINAGE SYSTEM THEY SHALL COMPLY WITH. FBC PL 802.1.6
 DOMESTIC DISHWASHING MACHINES.
 DOMESTIC DISHWASHING MACHINES SHALL DISCHARGE
 INDIRECTLY THROUGH AN AIR GAP OR AIR BREAK INTO A
 STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH SECTION
 802.2, OR DISCHARGE INTO A WYE-BRANCH FITTING ON THE
 TAILPIECE OF THE KITCHEN SINK OR THE DISHWASHER
 CONNECTION OF A FOOD WASTE GRINDER. THE WASTE LINE OF A
 DOMESTIC DISHWASHING MACHINE DISCHARGING INTO A KITCHEN
 SINK TAILPIECE OR FOOD WASTE GRINDER SHALL CONNECT TO A
 DECK-MOUNTED AIR GAP OR THE WASTE LINE SHALL RISE AND
 BE SECURELY FASTENED TO THE UNDERSIDE OF THE SINK RIM
 OR COUNTER.
  
 802.1.7 COMMERCIAL DISHWASHING MACHINES.
 THE DISCHARGE FROM A COMMERCIAL DISHWASHING MACHINE
 SHALL BE THROUGH AN AIR GAP OR AIR BREAK INTO A
 STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH SECTION
 802.2.
  
 5. A BACK FLOW DEVISE IS REQUIRED ON THE WATER SUPPLY
 FOR THE ICE MAKER. PER FBC PL 608.3
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  