Plan Review Notes
Plan Review Notes For Permit 17020277
Permit Number 17020277
Review Stop M
Sequence Number 1
Notes
Date Text
2017-02-09 14:34:001ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES
 PERMIT #17020277
 2/9/17
  
 1) THE PROPOSED PROJECT SHALL BE CLASSIFIED AS A CHANGE
 OF OCCUPANCY PER SECTION 506 FBC-14 EXISTING BUILDING.
 PLEASE CORRECT THE APPLICATION AND THE LEVEL 2
 ALTERATION CLASSIFICATION SHOWN ON SHEET LS-1. THE CITY
 OF WEST PALM BEACH BUSINESS LICENSING RECORDS SHOW NO
 LICENSURE FOR THE CHURCH, AND THE PALM BEACH COUNTY
 PROPERTY APPRAISER?S REPORT IDENTIFIES THE USE AS
 OFFICE
  
 2) REFER TO SECTION C101.4.4 AND C401.2 FBC-14 ENERGY
 CONSERVATION CODE, AND SUBMIT DOCUMENTATION OF
 COMPLIANCE.
  
 3) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW AC SYSTEMS- SECTION C403.2.1
  
 4) COMMISSIONING OF THE MECHANICAL AND ELECTRICAL
 LIGHTING SYSTEMS IS REQUIRED PER SECTION C408.1 AND
 C408.2. PLEASE PROVIDE A PLAN IN ACCORDANCE WITH
 SECTION C408.2.1 AND REVIEW ALL COMPLIANCES AS
 INDICATED IN THE SUB-SECTIONS OF C408.2. PLEASE NOTE
 THAT PRIOR TO PASSING THE FINAL MECHANICAL INSPECTION,
 THE REGISTERED DESIGN PROFESSIONAL SHALL PROVIDE
 EVIDENCE OF MECHANICAL SYSTEMS COMMISSIONING WHICH
 INCLUDES A FINAL REPORT.
  
 5) REFER TO SECTIONS 809.1 & 809.2 AND PROVIDE MINIMUM
 VENTILATION CALCULATIONS FOR ALL ROOMS AND SPACES PER
 TABLE 403.3 FBC-14 EXISTING BUILDING CODE. PROVIDE A
 SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED CFMS
 OF O/A AIR FOR OCCUPANTS. A) PLEASE NOTE THAT DEMAND
 CONTROLLED VENTILATION MAY BE REQUIRED PER SECTION
 C403.2.5.1.
  
 6) SHEET M-1: PROVIDE A KEYNOTE TO IDENTIFY THE 14X14
 EXHAUST DUCT FROM ERV-1.
  
 7) M-1: THE PLAN INDICATES 450 CFMS OF AIR BEING
 RETURNED FROM HALL A, HOWEVER THERE APPEARS TO BE NO
 AIR SUPPLIED TO HALL A- PLEASE CLARIFY.
  
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DOUBLE
 WALL AND CONVECTION OVENS.
  
 9) IN ORDER TO EXPEDITE THE SECOND REVIEW, PROVIDE A
 RESPONSE NARRATIVE FOR THE DESIGN PROFESSIONAL OF
 RECORD ADDRESSING EACH COMMENT. DUE TO THE LACK OF
 INFORMATION THE MECHANICAL REVIEW IS STOPPED AT THIS
 TIME. PLEASE NOTE ADDITIONAL COMMENTS MAY OCCUR UPON
 REVIEW OF THE CALCULATIONS AND THE RESUBMITTED PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER