| Date |
Text |
| 2017-02-09 14:34:00 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING, |
| | ENERGY CONSERVATION CODES |
| | PERMIT #17020277 |
| | 2/9/17 |
| | |
| | 1) THE PROPOSED PROJECT SHALL BE CLASSIFIED AS A CHANGE |
| | OF OCCUPANCY PER SECTION 506 FBC-14 EXISTING BUILDING. |
| | PLEASE CORRECT THE APPLICATION AND THE LEVEL 2 |
| | ALTERATION CLASSIFICATION SHOWN ON SHEET LS-1. THE CITY |
| | OF WEST PALM BEACH BUSINESS LICENSING RECORDS SHOW NO |
| | LICENSURE FOR THE CHURCH, AND THE PALM BEACH COUNTY |
| | PROPERTY APPRAISER?S REPORT IDENTIFIES THE USE AS |
| | OFFICE |
| | |
| | 2) REFER TO SECTION C101.4.4 AND C401.2 FBC-14 ENERGY |
| | CONSERVATION CODE, AND SUBMIT DOCUMENTATION OF |
| | COMPLIANCE. |
| | |
| | 3) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| | NEW AC SYSTEMS- SECTION C403.2.1 |
| | |
| | 4) COMMISSIONING OF THE MECHANICAL AND ELECTRICAL |
| | LIGHTING SYSTEMS IS REQUIRED PER SECTION C408.1 AND |
| | C408.2. PLEASE PROVIDE A PLAN IN ACCORDANCE WITH |
| | SECTION C408.2.1 AND REVIEW ALL COMPLIANCES AS |
| | INDICATED IN THE SUB-SECTIONS OF C408.2. PLEASE NOTE |
| | THAT PRIOR TO PASSING THE FINAL MECHANICAL INSPECTION, |
| | THE REGISTERED DESIGN PROFESSIONAL SHALL PROVIDE |
| | EVIDENCE OF MECHANICAL SYSTEMS COMMISSIONING WHICH |
| | INCLUDES A FINAL REPORT. |
| | |
| | 5) REFER TO SECTIONS 809.1 & 809.2 AND PROVIDE MINIMUM |
| | VENTILATION CALCULATIONS FOR ALL ROOMS AND SPACES PER |
| | TABLE 403.3 FBC-14 EXISTING BUILDING CODE. PROVIDE A |
| | SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED CFMS |
| | OF O/A AIR FOR OCCUPANTS. A) PLEASE NOTE THAT DEMAND |
| | CONTROLLED VENTILATION MAY BE REQUIRED PER SECTION |
| | C403.2.5.1. |
| | |
| | 6) SHEET M-1: PROVIDE A KEYNOTE TO IDENTIFY THE 14X14 |
| | EXHAUST DUCT FROM ERV-1. |
| | |
| | 7) M-1: THE PLAN INDICATES 450 CFMS OF AIR BEING |
| | RETURNED FROM HALL A, HOWEVER THERE APPEARS TO BE NO |
| | AIR SUPPLIED TO HALL A- PLEASE CLARIFY. |
| | |
| | 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DOUBLE |
| | WALL AND CONVECTION OVENS. |
| | |
| | 9) IN ORDER TO EXPEDITE THE SECOND REVIEW, PROVIDE A |
| | RESPONSE NARRATIVE FOR THE DESIGN PROFESSIONAL OF |
| | RECORD ADDRESSING EACH COMMENT. DUE TO THE LACK OF |
| | INFORMATION THE MECHANICAL REVIEW IS STOPPED AT THIS |
| | TIME. PLEASE NOTE ADDITIONAL COMMENTS MAY OCCUR UPON |
| | REVIEW OF THE CALCULATIONS AND THE RESUBMITTED PLANS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |