| Date |
Text |
| 2017-02-23 13:43:12 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) THE PROPOSED OCCUPANCY USE IS A CHANGE OF OCCUPANCY |
| | AND APPEARS TO BE ASSEMBLY. HOWEVER, THERE ARE SEVERAL |
| | OCCUPANCIES IN THIS PROJECT, ASSEMBLY, BUSINESS, |
| | EDUCATION, |
| | |
| | PER NFPA 101 |
| | |
| | 12.1.2* CLASSIFICATION OF OCCUPANCY. SEE 6.1.2. |
| | 12.1.3 MULTIPLE OCCUPANCIES. |
| | 12.1.3.1 GENERAL. MULTIPLE OCCUPANCIES SHALL BE IN |
| | ACCORDANCE WITH 6.1.14. |
| | |
| | 6.1.14 MULTIPLE OCCUPANCIES. |
| | 6.1.14.1 GENERAL. |
| | 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE |
| | REQUIREMENTS OF 6.1.14.1 AND ONE OF THE FOLLOWING: |
| | (1) MIXED OCCUPANCIES ? 6.1.14.3 |
| | (2) SEPARATED OCCUPANCIES ? 6.1.14.4 |
| | |
| | 6.1.14.2 DEFINITIONS. |
| | 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE |
| | IN WHICH TWO OR MORE CLASSES OF OCCUPANCY EXIST. |
| | 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE |
| | THE OCCUPANCIES ARE INTERMINGLED. |
| | 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY |
| | WHERE THE OCCUPANCIES ARE SEPARATED BY FIRE |
| | RESISTANCE?RATED ASSEMBLIES. |
| | 6.1.14.3 MIXED OCCUPANCIES. |
| | 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE |
| | CLASSIFIED AS TO ITS USE IN ACCORDANCE WITH SECTION 6.1 |
| | 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST |
| | RESTRICTIVE REQUIREMENTS OF THE OCCUPANCIES INVOLVED, |
| | UNLESS SEPARATE SAFEGUARDS ARE APPROVED. |
| | |
| | PLEASE PROVIDE THE SPECIFIC OCCPANY AND ENSURE ALL THE |
| | REQUIRMENTS OF THEAT OCCUPANCY ARE ADDRESSED. |
| | |
| | |
| | |
| | 2) SHEET A 4 - THERE ARE INDICATIONS OF WARMING OVENS |
| | IN THE KITCHEN. |
| | |
| | PER NFPA 101 |
| | |
| | 12.3.2.2 COOKING EQUIPMENT. COOKING EQUIPMENT SHALL BE |
| | PROTECTED IN ACCORDANCE WITH 9.2.3, UNLESS THE COOKING |
| | EQUIPMENT IS ONE OF THE FOLLOWING TYPES: |
| | (1) OUTDOOR EQUIPMENT |
| | (2) PORTABLE EQUIPMENT NOT FLUE-CONNECTED |
| | (3) EQUIPMENT USED ONLY FOR FOOD WARMING |
| | |
| | FOR VERIFICATION PURPOSES, PLEASE PROVIDE THE |
| | MANUFACTURES SPECIFICATION SHEETS FOR EACH OF THE |
| | WARMING OVENS. |
| | |
| | |
| | |
| | |
| | 3) SHEET A 3 - THE DOOR SCHEDULE INDCATES EXIT DEVICE |
| | KEY ENTRY |
| | |
| | PER NFPA 101 |
| | |
| | 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM |
| | AN AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS |
| | SHALL BE PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK |
| | ONLY IF THE LATCH OR LOCK IS PANIC HARDWARE OR FIRE |
| | EXIT HARDWARE COMPLYING WITH7.2.1.7, UNLESS OTHERWISE |
| | PERMITTED BY ONE OF THE FOLLOWING: |
| | (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS |
| | LOCKS AS PERMITTED IN 12.2.2.2.5. |
| | (2) THIS REQUIREMENT SHALL NOT APPLY TO |
| | ACCESS-CONTROLLED EGRESS DOORS AS PERMITTED IN |
| | 12.2.2.2.6. 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH |
| | 7.2.1.5.5 SHALL BE PERMITTED TO BE USED ON A SINGLE |
| | DOOR OR A SINGLE PAIR OF DOORS IF BOTH OF THE FOLLOWING |
| | CONDITIONS APPLY: |
| | (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT |
| | AND THE ASSEMBLY OCCUPANCY HAS AN OCCUPANT LOAD NOT |
| | GREATER THAN 500. |
| | (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN |
| | ASSEMBLY OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR |
| | MORE ARE RELEASED BY PANIC HARDWARE OR FIRE EXIT |
| | HARDWARE. |
| | |
| | PLEASE PROVIDE FOR THE NOTED REQUIREMENTS ON ALL |
| | APPLICABLE EXIT DOORS. |
| | |
| | |
| | |
| | 4) SHEET FP 1 - THE DESIGN OF THE FIRE SPRINKLER SYSTEM |
| | DOES NOT MEET THE REQUIRMENTS OF THE CODE |
| | |
| | FLORIDA BUILDING CODE |
| | |
| | 105.3.1.2 NO PERMIT MAY BE ISSUED FOR ANY BUILDING |
| | CONSTRUCTION, ERECTION, ALTERATION, MODIFICATION, |
| | REPAIR, OR ADDITION UNLESS THE APPLICANT FOR SUCH |
| | PERMIT PROVIDES TO THE ENFORCING AGENCY WHICH ISSUES |
| | THE PERMIT ANY OF THE FOLLOWING DOCUMENTS WHICH APPLY |
| | TO THE CONSTRUCTION FOR WHICH THE PERMIT IS TO BE |
| | ISSUED AND WHICH SHALL BE PREPARED BY OR UNDER THE |
| | DIRECTION OF AN ENGINEER REGISTERED UNDER CHAPTER 471, |
| | FLORIDA STATUTES: |
| | |
| | 2. FIRE SPRINKLER DOCUMENTS FOR ANY NEW BUILDING OR |
| | ADDITION WHICH INCLUDES A FIRE SPRINKLER SYSTEM WHICH |
| | CONTAINS 50 OR MORE SPRINKLER HEADS. PERSONNEL AS |
| | AUTHORIZED BY CHAPTER 633 FLORIDA STATUTES, MAY DESIGN |
| | A FIRE SPRINKLER SYSTEM OF 49 OR FEWER HEADS AND MAY |
| | DESIGN THE ALTERATION OF AN EXISTING FIRE SPRINKLER |
| | SYSTEM IF THE ALTERATION CONSISTS OF THE RELOCATION, |
| | ADDITION OR DELETION OF NOT MORE THAN 49 HEADS, |
| | NOTWITHSTANDING THE SIZE OF THE EXISTING FIRE SPRINKLER |
| | SYSTEM. |
| | |
| | FAC |
| | |
| | 61G15-32.003 COMMON REQUIREMENTS TO ALL FIRE PROTECTION |
| | ENGINEERING |
| | DOCUMENTS. |
| | (1) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS |
| | SHALL PROVIDE THE ENGINEERING REQUIREMENTS TO BE USED |
| | IN THE PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT |
| | DOCUMENTS AND TO INDICATE THE NATURE AND SCOPE OF THE |
| | WORK, AND TO DESCRIBE, DETAIL, DIMENSION, LABEL AND |
| | DEFINE THE FIRE PROTECTION COMPONENTS, SYSTEM(S), |
| | MATERIALS, ASSEMBLIES, EQUIPMENT AND ITS STRUCTURAL AND |
| | UTILITY SUPPORT SYSTEM(S), INSOFAR AS THEY INVOLVE THE |
| | SAFEGUARDING OF LIFE, HEALTH OR PROPERTY. |
| | (2) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS |
| | SHALL SPECIFY THE APPLICABLE REQUIREMENTS FOR THE |
| | ACCEPTANCE TESTING OF THE FIRE PROTECTION SYSTEM AND |
| | COMPONENTS, WHICH SHALL BE BASED UPON APPLICABLE CODES |
| | AND STANDARDS, WHERE AVAILABLE. |
| | (3) THE OCCUPANCY OF THE AREA OR DESCRIPTION OF A |
| | SPECIFIC HAZARD BEING PROTECTED BY THE FIRE PROTECTION |
| | SYSTEM(S) SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. |
| | (4) THE APPLICABLE CODE AND STANDARD TO BE USED IN THE |
| | PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT |
| | DOCUMENTS SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. WHEN CODES AND STANDARDS ARE NOT |
| | AVAILABLE OR APPLICABLE, AND SAID LAYOUT DOCUMENTS ARE |
| | TO BE BASED ON ENGINEERING JUDGMENT, ANY REASONS AND |
| | ASSUMPTIONS MADE TO DEVELOP THE FIRE PROTECTION CONCEPT |
| | SHALL BE IDENTIFIED ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. |
| | (5) STRUCTURAL SUPPORT AND STRUCTURAL OPENINGS REQUIRED |
| | BY THE FIRE PROTECTION SYSTEM SHALL BE SHOWN ON THE |
| | FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS AND SHALL |
| | BE REFERENCED ON STRUCTURAL ENGINEERING DOCUMENTS. |
| | (6) WHEN LAYOUT DOCUMENTS CONTAIN MATERIAL DEVIATION |
| | FROM THE ENGINEER OF RECORD'S FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENT, SUCH LAYOUT DOCUMENTS ARE NOT |
| | COMPLIANT UNLESS THEY ARE ACCOMPANIED BY REVISED |
| | ENGINEERING DOCUMENTS MADE AND SEALED BY THE ENGINEER |
| | OF RECORD FOR THE FIRE PROTECTION SYSTEM. |
| | (7) REQUIREMENTS FOR ACTIVATION CONTROL SYSTEMS, |
| | SEQUENCE, OPERATING PARAMETERS, INTERLOCKS, SAFETY |
| | RELATED DEVICES, INDICATORS AND ALARMS, SHALL BE SHOWN |
| | ON THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS, |
| | UNLESS SHOWN ON OTHER RELATED DOCUMENTS. |
| | (8) ANY INFORMATION DEEMED APPROPRIATE BY THE ENGINEER |
| | OF RECORD TO ASSIST THE AUTHORITY HAVING JURISDICTION |
| | IN UNDERSTANDING THE OWNER?S INTENDED USE AND PROPOSED |
| | PROTECTION OF THE BUILDING OR FACILITY AND TO PROVIDE |
| | SUFFICIENT DIRECTION TO THE INSTALLATION CONTRACTOR OR |
| | OTHER INTERESTED PARTIES REGARDING THE LAYOUT OF THE |
| | SYSTEM(S), SHALL BE INCLUDED IN THE FIRE PROTECTION |
| | SYSTEM ENGINEERING DOCUMENTS. |
| | SPECIFIC AUTHORITY 471.008, 471.033(2), FS |
| | LAW IMPLEMENTED 471.005(7), 471.033(2), FS |
| | HISTORY?NEW 5-19-93, FORMERLY 21H-32.003, AMENDED |
| | 4-2-2000, 6-26-01 |
| | |
| | 61G15-32.004 DESIGN OF WATER BASED FIRE PROTECTION |
| | SYSTEMS. |
| | (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT |
| | ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET, |
| | DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE |
| | CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE |
| | WATER MAINS AND DEDICATED FIRE PROTECTION WATER |
| | SOURCES. |
| | (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION |
| | SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL |
| | INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN |
| | APPLICABLE: |
| | (A) THE POINT OF SERVICE FOR THE FIRE PROTECTION WATER |
| | SUPPLY AS DEFINED BY 633.021(18) F.S. |
| | (B) APPLICABLE NFPA STANDARD TO BE APPLIED, OR IN THE |
| | CASE WHERE NO SUCH STANDARD EXISTS, THE ENGINEERING |
| | STUDY, JUDGMENTS, AND/OR PERFORMANCE BASED ANALYSIS AND |
| | CONCLUSIONS. |
| | (C) CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA. |
| | (D) DESIGN APPROACH, WHICH INCLUDES SYSTEM TYPE, |
| | DENSITIES, DEVICE TEMPERATURE RATING, AND SPACING FOR |
| | EACH SEPARATE 42 HAZARD OCCUPANCY. |
| | (E) CHARACTERISTICS OF WATER SUPPLY TO BE USED, SUCH AS |
| | MAIN SIZE AND LOCATION, WHETHER IT IS DEAD-END OR |
| | CIRCULATING; AND IF DEAD-END, THE DISTANCE TO THE |
| | NEAREST CIRCULATING MAIN, AS WELL AS ITS MINIMUM |
| | DURATION AND RELIABILITY FOR THE MOST HYDRAULICALLY |
| | DEMANDING DESIGN AREA. |
| | (F) WHEN PRIVATE OR PUBLIC WATER SUPPLIES ARE USED, THE |
| | FLOW TEST DATA, INCLUDING DATE AND TIME OF TEST, WHO |
| | CONDUCTED TEST OR SUPPLIED INFORMATION, TEST ELEVATION, |
| | STATIC GAUGE PRESSURE AT NO FLOW, FLOW RATE WITH |
| | RESIDUAL GAUGE PRESSURE, HYDRANT BUTT COEFFICIENT, AND |
| | LOCATION OF TEST IN RELATION TO THE HYDRAULIC POINT OF |
| | SERVICE. |
| | (G) VALVING AND ALARM REQUIREMENTS TO MINIMIZE |
| | POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF |
| | WATER. |
| | (H) MICROBIAL INDUCED CORROSION (MIC). THE ENGINEER OF |
| | RECORD SHALL MAKE REASONABLE EFFORTS TO IDENTIFY WATER |
| | SUPPLIES THAT COULD LEAD TO MICROBIAL INDUCED CORROSION |
| | (MIC). SUCH EFFORTS MAY CONSIST OF DISCUSSIONS WITH THE |
| | LOCAL WATER PURVEYOR AND/OR FIRE OFFICIAL, FAMILIARITY |
| | WITH CONDITIONS IN THE LOCAL AREA, OR LABORATORY |
| | TESTING OF WATER SUPPLIES. WHEN CONDITIONS ARE FOUND |
| | THAT MAY RESULT IN MIC CONTAMINATION OF THE FIRE |
| | PROTECTION PIPING, THE ENGINEER SHALL DESIGN CORRECTIVE |
| | MEASURES. |
| | (I) BACKFLOW PREVENTION AND METERING SPECIFICATIONS AND |
| | DETAILS TO MEET LOCAL WATER PURVEYOR REQUIREMENTS |
| | INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP. |
| | (J) QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD |
| | AND INTERIOR FIRE PROTECTION COMPONENTS. |
| | (3) CONTRACTOR SUBMITTALS WHICH DEVIATE FROM THE ABOVE |
| | MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED MATERIAL |
| | DEVIATIONS AND REQUIRE SUPPLEMENTAL ENGINEERING |
| | APPROVAL AND DOCUMENTATION. |
| | (4) IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE |
| | INFORMATION AND DIRECTION THAN IS ESTABLISHED ABOVE, HE |
| | OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL |
| | ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE |
| | CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES. |
| | SPECIFIC AUTHORITY 471.008, 471.033(2), FS |
| | LAW IMPLEMENTED 471.005(7), 471.033(2), FS |
| | HISTORY?NEW 5-19-93, FORMERLY 21H-32.004, AMENDED |
| | 4-2-2000, 6-26-01, 7-12-05 |
| | |
| | PLEASE PROVIDE THE REQUIRED DOCUMENTATION EITHER IN |
| | PLAN DRAWINGS OR NARRATIVE FORM SIGNED AND SEALED BY A |
| | QUALIFIED EOR. |
| | |
| | |
| | |
| | |
| | 5) SHEET A 3 - THERE IS EXITING THROUGH A CLASSROOM B |
| | AT DOOR 27 THROUGH OFFICE 2, DOOR 53. THERE ARE |
| | LOCKSETS INDICATED FOR THESE DOORS. |
| | |
| | PER NFPA 101 |
| | |
| | 7.5.2 IMPEDIMENTS TO EGRESS. SEE ALSO 7.1.9 AND |
| | 7.2.1.5. |
| | 7.5.2.1* ACCESS TO AN EXIT SHALL NOT BE THROUGH |
| | KITCHENS, STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS |
| | 36 AND 37, RESTROOMS, WORKROOMS, CLOSETS, BEDROOMS OR |
| | SIMILAR SPACES, OR OTHER ROOMS OR SPACES SUBJECT TO |
| | LOCKING, UNLESS PASSAGE THROUGH SUCH ROOMS OR SPACES IS |
| | PERMITTED FOR THE OCCUPANCY BY CHAPTER 18, 19, 22, OR |
| | 23. |
| | |
| | THIS IS NOT ALLOWED WITHIN CHAPTER 12 NEW ASSEMBLY |
| | OCCUPANCIES. |
| | |
| | PLEASE PROVIDE DOOR KNOBS/HANDLES COMPLYING WITH THIS |
| | CODE. |
| | |
| | |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |