Plan Review Notes
Plan Review Notes For Permit 17020277
Permit Number 17020277
Review Stop E
Sequence Number 1
Notes
Date Text
2017-02-17 10:06:01INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL
 LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE
 ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS. A NOTE
 WILL SUFFICE.
 2. ADD A GENERAL NOTE TO PROVIDE PER FBC EC 405.7.4-
 COMPLETION DOCUMENTS PER CODE SECTION. FBC EC 405.7.3-
 VOLTAGE DROP
 3. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS
 MODIFICATIONS; SEE VERBIAGE IN CODE.
 4. PER FBC EC 405.7- A MINIMUM OF 50% OF ALL 125V, 15
 AND 20AMP RECEPTACLES SHALL BE AUTOMATICALLY CONTROLLED
 WHERE INSTALLED IN PRIVATE OR OPEN OFFICES AND COMPUTER
 CLASSROOMS. THIS INCLUDES MODULAR PARTITIONS TOO. SHOW
 COMPLIANCE ACCORDINGLY.
 5. SHOW ACTUAL CALCULATION AND COMPLIANCE WITH FBC
 ENERGY CONSERVATION LIGHTING DENSITIES PER CODE
 SECTION. C405
 6. LABEL ALL KITCHEN AREA RECEPTACLES WITHIN 6FT OF
 SINKS TO BE GFCI PROTECTED NEC 210.8B
 7. PLEASE ADDRESS BUILDING, FIRE AND MECHANICAL
 COMMENTS RELATED TO ELECTRICAL.
 8. DESIGNER OF RECORD TO SIGN AND SEAL ELECTRICAL
 DRAWINGS SUBMITTED FOR REVIEW.
 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  