| 2017-02-17 10:06:01 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 |
| | COMMENTS: |
| | |
| | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE |
| | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE |
| | PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL |
| | LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE |
| | ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS. A NOTE |
| | WILL SUFFICE. |
| | 2. ADD A GENERAL NOTE TO PROVIDE PER FBC EC 405.7.4- |
| | COMPLETION DOCUMENTS PER CODE SECTION. FBC EC 405.7.3- |
| | VOLTAGE DROP |
| | 3. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO |
| | INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC |
| | 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS |
| | MODIFICATIONS; SEE VERBIAGE IN CODE. |
| | 4. PER FBC EC 405.7- A MINIMUM OF 50% OF ALL 125V, 15 |
| | AND 20AMP RECEPTACLES SHALL BE AUTOMATICALLY CONTROLLED |
| | WHERE INSTALLED IN PRIVATE OR OPEN OFFICES AND COMPUTER |
| | CLASSROOMS. THIS INCLUDES MODULAR PARTITIONS TOO. SHOW |
| | COMPLIANCE ACCORDINGLY. |
| | 5. SHOW ACTUAL CALCULATION AND COMPLIANCE WITH FBC |
| | ENERGY CONSERVATION LIGHTING DENSITIES PER CODE |
| | SECTION. C405 |
| | 6. LABEL ALL KITCHEN AREA RECEPTACLES WITHIN 6FT OF |
| | SINKS TO BE GFCI PROTECTED NEC 210.8B |
| | 7. PLEASE ADDRESS BUILDING, FIRE AND MECHANICAL |
| | COMMENTS RELATED TO ELECTRICAL. |
| | 8. DESIGNER OF RECORD TO SIGN AND SEAL ELECTRICAL |
| | DRAWINGS SUBMITTED FOR REVIEW. |
| | 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE |
| | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING |
| | THIS PROJECT. |
| | |
| | |