| 2017-03-22 15:10:11 | REVIEW #2: COMMENTS HAVE NOT BEEN ADDRESSED. |
| | |
| | |
| | 4850 LORING DRIVE - PHASE II |
| | TRACKING #17020274 |
| | PERMIT #16070228 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE PLANS INDICATE THE USE OF THE ROOM DESIGN METHOD; |
| | HOWEVER, THE HYDRAULIC CALCULATION INFORMATION BLOCKS |
| | INDICATE THE USE OF THE AREA DENSITY METHOD. WHICH IS |
| | CORRECT? |
| | |
| | PLANS DO NOT SHOW THE FIRE RESISTANCE RATINGS OF ALL |
| | WALLS. |
| | |
| | ARE ALL ROOM AND CLOSET DOORS EQUIPPED WITH DOOR |
| | CLOSERS? IF NO, CALCULATING 5 SPRINKLERS IN THE |
| | HYDRAULIC AREA WOULD NOT BE CORRECT. SEVERAL AREAS |
| | RESULT IN THE FLOW OF 8, 9 OR GREATER SPRINKLERS FLOWS |
| | EVEN WHEN ATTEMPTING TO UTILIZE THE ROOM DESIGN METHOD. |
| | |
| | IF UTILIZING THE ROOM DESIGN METHOD, THE FOLLOWING |
| | REQUIREMENTS APPLY AND HAVE NOT BEEN MET ON THE CURRENT |
| | SET OF PLANS: |
| | |
| | 11.2.3.3 ROOM DESIGN METHOD |
| | TO UTILIZE THE ROOM DESIGN METHOD, ALL ROOMS SHALL BE |
| | ENCLOSED WITH WALLS HAVING A FIRE-RESISTANCE RATING |
| | EQUAL TO THE WATER SUPPLY DURATION INDICATED IN TABLE |
| | 11.2.3.1.2. |
| | |
| | MINIMUM PROTECTION OF OPENINGS SHALL BE AS FOLLOWS: |
| | |
| | (1) LIGHT HAZARD ? NONRATED AUTOMATIC OR SELF-CLOSING |
| | DOORS. |
| | (2) LIGHT HAZARD WITH NO OPENING PROTECTION ? WHERE |
| | OPENINGS ARE NOT PROTECTED, CALCULATIONS SHALL INCLUDE |
| | THE SPRINKLERS IN THE ROOM PLUS TWO SPRINKLERS IN THE |
| | COMMUNICATING SPACE NEAREST EACH SUCH UNPROTECTED |
| | OPENING UNLESS THE COMMUNICATING SPACE HAS ONLY ONE |
| | SPRINKLER, IN WHICH CASE CALCULATIONS SHALL BE EXTENDED |
| | TO THE OPERATION OF THAT SPRINKLER. THE SELECTION OF |
| | THE ROOM AND COMMUNICATING SPACE SPRINKLERS TO BE |
| | CALCULATED SHALL BE THAT WHICH PRODUCES THE GREATEST |
| | HYDRAULIC DEMAND. |
| | (3) ORDINARY AND EXTRA HAZARD ? AUTOMATIC OR |
| | SELF-CLOSING DOORS WITH APPROPRIATE FIRE RESISTANCE |
| | RATINGS FOR THE ENCLOSURE. |
| | |
| | OTHER THAN THE ROOF AREA, NO HYDRAULIC CALCULATIONS |
| | SUBMITTED FOR AREAS OUTSIDE OF THE DWELLING UNITS. |
| | |
| | A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED |
| | AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON |
| | THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED DURING PLAN RESUBMISSION. |
| | |