Plan Review Notes
Plan Review Notes For Permit 17020177
Permit Number 17020177
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-02-22 12:43:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) GENERAL COMMENT: HOW WILL THE WATER SUPPLY BE
 CONTROLLED DURING THE PHASING PLAN AND TCO AREAS? I.E.
 THE PARKING STRUCTURE WANTS TO BE TCO FOR FLOORS 1-6,
 HOW WILL THE WATER SUPPLY BE INSURED/CONTROLLED TO
 REMAIN ACTIVE, AS WELL AS, BEING AVAILABLE FOR FD USE
 ON ALL OTHER ARES DURING CONSTRUCTION? HOIW WILL FDC'S
 BE ASSIGNED, ETC.
  
 PLEASE PROVIDE A SPECIFIC DETAILED PLAN IN NARRATIVE
 AND/OR DRAWING FORM.
  
  
  
 2) SHEET FP 1.1 AND ALL OTHER RELATED PLAN SHEETS - THE
 SPRINKLER COUNT LEGEND INDICATES A FEW INCORRECT
 REFERENCES. A FEW DESCRIPTIONS DO NOT APPEAR TO MATCH
 THE PICTURE DIAGRAM.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 3) FP SHEETS & FP 17 - PRV'S ARE INDICATED; HOWEVER,
 THE SIZE AND/OR THE AMOUNT OF PRESSURE IS NOT.
  
 PLEASE PROVIDE THE SIZE AND/OR AMOUNT OF THE PRV FOR
 EACH AREA AND EACH FLOOR.
  
  
  
  
 4) FP SHEETS - SOME OF THE RESEDENTIAL UNITS APPEAR TO
 HAVE SOFFITS AND OR OTHER POTENTIAL OBSTRUCTION, I.E.
 CEILING FANS, LIGHT FIXTURES, ETC. WEHN SIDEWALL
 SPRINKLERS ARE INDICATED. RESIDENTIAL SIDEWALL
 SPRINKLERS ARE DESIGNED FOR FLAT CEILINGS.
  
 PLEASE PROVIDE A NOTE ENSURING COMPLIANCE WITH THE
 OBSTRUCTION REQUIRMENTS.
  
  
  
 5) FP SHEETS 13-24 -WITHIN THE SOUTH/CENTER UNITS IT
 APPEARS THAT A SIDEWALL SPRINKLER IS INDICATED IN A
 SMALL RECTANGLAR AREA NEXT TO CORRIDOR. IT DOES NOT
 APPEAR THAT A SIDEWALL SPRINKLER WILL WORK IN THIS
 AREA.
  
 PLEASE CONFIRM WHAT THIS AREA IS AND THAT A SIDEWALL
 SPRINKLER MEETS THE PROTECTION REQUIREMENTS.
  
  
  
  
 6) SHEET FP 13 - CONTAINED WITHIN THE AREA 1 LEVEL 24
 CALCULATION BOX 4 HEADS ARE INDICATED; HOWEVER, ONLY 2
 HEADS APPEAR TO BE CONTAINED WITHIN THE FLOOR AREA
 STRIPING.
  
 PLEASE REVIEW AND PROVIDE CLARITY, EXPLANATION OR
 CORRECT.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  