| Plan Review Notes For Permit 17020094 |
| Permit Number |
17020094 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-06-02 08:00:58 | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | | | PREVIOUS COMMENTS NOT ADDRESSED: | | | | | | "PROVIDE AN ACTUAL ONE-LINE DIAGRAM REFLECTING EXISTING | | | INSTALLATION, WITH CONDUCTOR SIZES, GROUNDS, ETC AND | | | AMP SIZE.. SHOW AN INTERSYSTEM BONDING TERMINAL AND | | | GROUNDING ELECTRODE CONDUCTOR SIZE. VERIFY IF THERE ARE | | | EXISTING SMOKE DETECTOR IN DWELLING. FBC RES 314-315, | | | FBC 107.3.5" | | | | | | 1. PROVIDE ONE-LINE (RISER) DIAGRAM AS PREVIOUSLY | | | REQUESTED. NEC 215.5 , FBC 107.3.5 | | | 2. SHOW INTERSYSTEM BONDING TERMINAL IN RISER DIAGRAM | | | AND GROUNDING ELECTRODE CONDUCTOR. NEC 250.66, 250.94 | | | 3. SHOW EXISTING SMOKE ALARMS ON PLAN. IF NONE ARE | | | EXISTING, OR NOT TO CODE, SHOW AS NEW INSTALLATION. FBC | | | R314, R315. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|