Plan Review Notes
Plan Review Notes For Permit 17020094
Permit Number 17020094
Review Stop E
Sequence Number 2
Notes
Date Text
2017-06-02 08:00:58CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 PREVIOUS COMMENTS NOT ADDRESSED:
  
 "PROVIDE AN ACTUAL ONE-LINE DIAGRAM REFLECTING EXISTING
 INSTALLATION, WITH CONDUCTOR SIZES, GROUNDS, ETC AND
 AMP SIZE.. SHOW AN INTERSYSTEM BONDING TERMINAL AND
 GROUNDING ELECTRODE CONDUCTOR SIZE. VERIFY IF THERE ARE
 EXISTING SMOKE DETECTOR IN DWELLING. FBC RES 314-315,
 FBC 107.3.5"
  
 1. PROVIDE ONE-LINE (RISER) DIAGRAM AS PREVIOUSLY
 REQUESTED. NEC 215.5 , FBC 107.3.5
 2. SHOW INTERSYSTEM BONDING TERMINAL IN RISER DIAGRAM
 AND GROUNDING ELECTRODE CONDUCTOR. NEC 250.66, 250.94
 3. SHOW EXISTING SMOKE ALARMS ON PLAN. IF NONE ARE
 EXISTING, OR NOT TO CODE, SHOW AS NEW INSTALLATION. FBC
 R314, R315.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  