| 2017-02-06 13:21:29 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: |
| | JOB ADDRESS: 306 MARLBORO PL |
| | DESCRIPTION: COMPLETE INTERIOR REMODEL |
| | MASTER PERMIT: 17020082 |
| | |
| | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| | SUBMITTED CORRECTIONS. |
| | 1. ELECTRICAL SUB PERMIT REQUIRED. |
| | 2. A SITE PLAN INDICATING THE LOCATION OF THE ELECTRIC |
| | SERVICE UTILITY POLE AND ELECTRICAL METERS SHALL BE |
| | SUBMITTED. |
| | 3. FBC-RE 3601: SERVICE DISCONNECT SHALL BE SHOWN ON |
| | FLOORPLAN. IT SHALL BE MARKED AS REQUIRED. |
| | 4. FBC-RE 3602: SERVICE LOAD SHALL BE CALCULATED AS |
| | INSTRUCTED AND SHOWN ON PLANS. |
| | 5. FBC-RE 3609: THE INTERSYSTEM BONDING TERMINAL SHALL |
| | BE INCLUDED AND SHOW ON THE SERVICE DIAGRAM. |
| | 6. FBC-RE 3704: A SERVICE LOAD DIAGRAM SHALL BE |
| | PROVIDED AND A SERVICE DIAGRAM IS REQUIRED TO DETERMINE |
| | PROPER SIZING OF FEEDER CONDUCTORS. |
| | 7. FBC-RE 3705: THE LOCATION OF ALL ELECTRICAL PANELS |
| | SHALL BE MARKED ON THE FLOORPLANS. |
| | 8. FBC-RE 3902: ARC-FAULT REQUIREMENTS EXTEND BEYOND |
| | THE BEDROOMS AS MENTIONED ON PLANS. CORRECT |
| | ACCORDINGLY. |
| | 9. FBC-RE 3901: TO COMPLY WITH THE OUTLET SPACING |
| | REQUIREMENTS OF THIS SECTION THERE IS AN OUTLET MISSING |
| | IN THE MASTER BEDROOM AND IN BEDROOM #2. |
| | 10. FBC-RE 3901: YOU SHALL MARK ON THE FLOORPLAN THE |
| | LOCATION OF ALL HVAC EQUIPMENT AND SHOW THE REQUIRED |
| | SERVICE OUTLETS AND ILLUMINATION. |
| | 11. FBC-RE 3905: CEILING BOXES FOR THE SUPPORT OF |
| | PADDLE FANS SHALL BE LISTED FOR THE PURPOSE AND MARKED |
| | ACCORDINGLY. |
| | 12. FBC-RE4001: THE GROUNDED CONDUCTOR SHALL BE |
| | PROVIDED AT THE SWITCH AS REQUIRED. |
| | 13. FBC-RE4002: TAMPER-RESISTANT RECEPTACLES SHALL BE |
| | PROVIDED THROUGHOUT THE RESIDENCE. |
| | 14. FBC-RE4003: RECESSED INCANDESCENT LUMINAIRES SHALL |
| | HAVE THERMAL PROTECTION AND SHALL BE LISTED AS |
| | THERMALLY PROTECTED. |
| | 15. FBC-ER404.1 A MINIMUM OF 75% OF THE LAMPS IN |
| | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE |
| | HIGH-EFFICACY LAMPS OR A MINIMUM OF 75% OF THE |
| | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN |
| | ONLY HIGH EFFICIENCY LAMPS. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |