Plan Review Notes
Plan Review Notes For Permit 17020076
Permit Number 17020076
Review Stop M
Sequence Number 1
Notes
Date Text
2017-03-03 09:35:411ST REVIEW FBC-2014 MECHANICAL
 REVISION PERMIT #17020076
 3/3/17
  
 1) SHEET M-101: PLEASE REVISE KEY NOTE #9 TO INDICATE A
 DRAIN PAN UNDER THE UNIT WILL BE EQUIPPED WITH A
 ?WATER-LEVEL DETECTION DEVICE CONFORMING TO UL 508?
 ?SECTION 307.2.3 FBC-14 MECHANICAL.
  
 2) M-101, M-102, M-103: CLARIFY WHY THE MAIN RETURN
 DUCT AT EACH FLOOR LEVEL AND THE RISER IN GENERAL HAS
 BEEN REDUCED IN SIZE AND SHOW BOTH THE TOTAL RETURN AND
 SUPPLY CFMS AT EACH FLOOR LEVEL.
  
 3) M-101: THE NEW LOCKER ROOM REQUIRES AN EXHAUST
 SYSTEM SIZED AT .25 CFMS PER SQ. FT.
  
 4) M-102: INDICATE HOW AIR WILL BE RETURNED FROM THE
 NEW SWATCH ROOM. PLEASE REVIEW ALL LEVELS TO VERIFY ALL
 ENCLOSED ROOMS ARE EQUIPPED WITH RETURNS WHERE
 REQUIRED.
  
 5) M-102: PLEASE CLOUD THE LOCATION OF THE JANITOR?S
 CLOSET AND PROVIDE AN EXHAUST SYSTEM PER TABLE 6-4
 ASHRAE 62.1-2010.
  
 6) M-103: INDICATE THE SIZES OF THE SUPPLY DUCT RISERS
 FROM VRV 52 & 53.
  
 7) M-104: PROVIDE THE BRANCH DUCT SIZES SUPPLYING THE
 REGISTERS IN THE RESTAURANT.
  
 8) M-301: PLEASE NOTE THAT TABLE 6-4 ASHRAE 62.1-2010
 REQUIRES AN EXHAUST SYSTEM SIZED AT 1.00 CFM PER SQ.
 FT. FOR THE TRASH ROOM. ASHRAE 62.1 IS REFERENCED IN
 THE FBC-14 MECHANICAL CODE
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  