| 2017-03-03 09:35:41 | 1ST REVIEW FBC-2014 MECHANICAL |
| | REVISION PERMIT #17020076 |
| | 3/3/17 |
| | |
| | 1) SHEET M-101: PLEASE REVISE KEY NOTE #9 TO INDICATE A |
| | DRAIN PAN UNDER THE UNIT WILL BE EQUIPPED WITH A |
| | ?WATER-LEVEL DETECTION DEVICE CONFORMING TO UL 508? |
| | ?SECTION 307.2.3 FBC-14 MECHANICAL. |
| | |
| | 2) M-101, M-102, M-103: CLARIFY WHY THE MAIN RETURN |
| | DUCT AT EACH FLOOR LEVEL AND THE RISER IN GENERAL HAS |
| | BEEN REDUCED IN SIZE AND SHOW BOTH THE TOTAL RETURN AND |
| | SUPPLY CFMS AT EACH FLOOR LEVEL. |
| | |
| | 3) M-101: THE NEW LOCKER ROOM REQUIRES AN EXHAUST |
| | SYSTEM SIZED AT .25 CFMS PER SQ. FT. |
| | |
| | 4) M-102: INDICATE HOW AIR WILL BE RETURNED FROM THE |
| | NEW SWATCH ROOM. PLEASE REVIEW ALL LEVELS TO VERIFY ALL |
| | ENCLOSED ROOMS ARE EQUIPPED WITH RETURNS WHERE |
| | REQUIRED. |
| | |
| | 5) M-102: PLEASE CLOUD THE LOCATION OF THE JANITOR?S |
| | CLOSET AND PROVIDE AN EXHAUST SYSTEM PER TABLE 6-4 |
| | ASHRAE 62.1-2010. |
| | |
| | 6) M-103: INDICATE THE SIZES OF THE SUPPLY DUCT RISERS |
| | FROM VRV 52 & 53. |
| | |
| | 7) M-104: PROVIDE THE BRANCH DUCT SIZES SUPPLYING THE |
| | REGISTERS IN THE RESTAURANT. |
| | |
| | 8) M-301: PLEASE NOTE THAT TABLE 6-4 ASHRAE 62.1-2010 |
| | REQUIRES AN EXHAUST SYSTEM SIZED AT 1.00 CFM PER SQ. |
| | FT. FOR THE TRASH ROOM. ASHRAE 62.1 IS REFERENCED IN |
| | THE FBC-14 MECHANICAL CODE |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |