| 2017-03-22 14:40:12 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1. FOURTH FLOOR, RESTAURANT AND WINE VAULT, REVISED |
| | PLAN SHOWS SEATING. IS ANY OF THIS TO BE FIXED SEATING? |
| | FBC A 226, 902, REVISE PLAN TO CLARIFY AND PROVIDE |
| | DETAILS IF APPLICABLE. |
| | |
| | 2. A050, J3-A107, IT APPEARS THAT OCCUPANTS OF THE |
| | FOURTH FLOOR A2 OCCUPANCY EXIT THROUGH THE STAIRS, THEN |
| | THR0UGH THE NORTH AND SOUTH GATES. FBC 1008.1.10, |
| | 1008.2, REVISE TO INCLUDE THE FIRE EXIT OR PANIC |
| | HARDWARE REQUIRED, OR CLARIFY EXIT DISCHARGE FOR |
| | ASSEMBLY OCCUPANCY. |
| | |
| | 3. 1ST FLOOR, REVISE PLAN TO CLARIFY USE OF LOCKERS. IT |
| | IS NOT CLEAR WHETHER OR NOT ACCESSIBILITY APPLIES; FBC |
| | A 803. IF ACCESSIBILITY APPLIES, THIS REVISION CAN BE |
| | ISSUED (UPON REQUEST) WITH A PROVISO THAT DETAILS BE |
| | PROVIDED PRIOR TO INSTALLATION. |
| | |
| | BREAKROOM 123 SHOWS LOCKERS. LOCKERS ARE TO BE |
| | ACCESSIBLE, FBC A 803; THIS REVISION WILL BE ISSUED |
| | WITH PROVISO THAT A DETAILS SHOWING COMPLIANCE BE |
| | PROVIDED AT INSPECTION. SUBJECT TO FIELD INSPECTOR'S |
| | DISCRETION, A SUBMITTAL OR REVISION MAY BE REQUIRED. |
| | |
| | HTTPS://WWW.ACCESS-BOARD.GOV/GUIDELINES-AND-STANDARDS/R |
| | ECREATION-FACILITIES/GUIDES/SPORTS-FACILITIES/DRESSING, |
| | -FITTING,-OR-LOCKER-ROOMS |
| | |
| | 4. A120A AND OTHER SHEETS, WOMENS WC 471, DOOR 471.3 |
| | APPEARS TO OBSTRUCT THE MANEUVERING CLEARANCE FOR DOOR |
| | 471.2, REVISE, FBC A 404.2.4. |
| | |
| | 5. IT APPEARS THAT THERE IS AN ADDITION OF SQUARE FOOT |
| | AREA. REVISE PLAN TO CLARIFY OLD TOTAL, NEW TOTAL. |
| | BUILDING DATA NEEDS TO BE UPDATED, BOTH ON THE PLAN AND |
| | IN OUR SYSTEM FOR RECORDKEEPING AND CO, AND ADDITIONAL |
| | IMPACT FEES MAY BE DUE. SEE IMPACT FEE REVIEW. |
| | |
| | 6. THE ARCHITECTURAL SHEETS HAVE AN ERROR THAT |
| | "CERTIFICATION IS INVALID", BUT THE SIGNATURE SHOWS |
| | THAT IT WAS SIGNED BY WILLIAM HOBBS. PLEASE CONTACT |
| | ISSUER AND PROVIDE INFORMATION REGARDING THIS ERROR. |
| | PLEASE DO NOT UPLOAD NEW SHEETS UNLESS THEY ARE REVISED |
| | TO ADDRESS PLAN REVIEW COMMENTS, OR IF THE ISSUER OF |
| | DIGITAL SEAL/SIGNATURE ADVISES THAT SHEETS NEED TO BE |
| | RE-SIGNED/SEALED. FAC61G15-30, FS481. |
| | |
| | 7. D3-A422 (AND POSSIBLY OTHER LOCATIONS) SPECS PT |
| | PLYWOOD. THIS IS A TYPE II BUILDING; SEE FBC B 603.1. |
| | IF DOR FEELS THIS FALLS UNDER AN EXCEPTION, REVISE |
| | DETAIL TO INCLUDE EXCEPTION AND SQUARE FOOT AREA |
| | AFFECTED. SEND VIA EMAIL FOR PRELIMINARY REVIEW AND |
| | ACCEPTANCE PRIOR TO RESUBMITTAL. |
| | |
| | 8. MANY SHEETS REVIEWED APPEAR TO AFFECT OTHER PERMITS. |
| | FOR INSTANCE, THE HARDSCAPE REVIEWED UNDER THIS |
| | REVISION APPEARS TO AFFECT THE HARDSCAPE PERMIT |
| | 16010525. AFTER THIS REVISION IS REVIEWED, COORDINATE |
| | WITH STEVE KENNEDY (OR WITH ME IF HE IS NOT AVAILABLE) |
| | TO HAVE THE OTHER PERMITS UPDATED. ADDITIONAL REVISIONS |
| | ARE NOT REQUIRED. |
| | |
| | 9. PRIOR TO RESUBMITTAL, OR SUBMITTAL OF OTHER PERMITS |
| | AND/OR REVISIONS, CONTACT STEVE KENNEDY TO COORDINATE |
| | FEES. |
| | |