Plan Review Notes
Plan Review Notes For Permit 17020076
Permit Number 17020076
Review Stop B
Sequence Number 1
Notes
Date Text
2017-03-22 14:40:12****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FOURTH FLOOR, RESTAURANT AND WINE VAULT, REVISED
 PLAN SHOWS SEATING. IS ANY OF THIS TO BE FIXED SEATING?
 FBC A 226, 902, REVISE PLAN TO CLARIFY AND PROVIDE
 DETAILS IF APPLICABLE.
  
 2. A050, J3-A107, IT APPEARS THAT OCCUPANTS OF THE
 FOURTH FLOOR A2 OCCUPANCY EXIT THROUGH THE STAIRS, THEN
 THR0UGH THE NORTH AND SOUTH GATES. FBC 1008.1.10,
 1008.2, REVISE TO INCLUDE THE FIRE EXIT OR PANIC
 HARDWARE REQUIRED, OR CLARIFY EXIT DISCHARGE FOR
 ASSEMBLY OCCUPANCY.
  
 3. 1ST FLOOR, REVISE PLAN TO CLARIFY USE OF LOCKERS. IT
 IS NOT CLEAR WHETHER OR NOT ACCESSIBILITY APPLIES; FBC
 A 803. IF ACCESSIBILITY APPLIES, THIS REVISION CAN BE
 ISSUED (UPON REQUEST) WITH A PROVISO THAT DETAILS BE
 PROVIDED PRIOR TO INSTALLATION.
  
 BREAKROOM 123 SHOWS LOCKERS. LOCKERS ARE TO BE
 ACCESSIBLE, FBC A 803; THIS REVISION WILL BE ISSUED
 WITH PROVISO THAT A DETAILS SHOWING COMPLIANCE BE
 PROVIDED AT INSPECTION. SUBJECT TO FIELD INSPECTOR'S
 DISCRETION, A SUBMITTAL OR REVISION MAY BE REQUIRED.
  
 HTTPS://WWW.ACCESS-BOARD.GOV/GUIDELINES-AND-STANDARDS/R
 ECREATION-FACILITIES/GUIDES/SPORTS-FACILITIES/DRESSING,
 -FITTING,-OR-LOCKER-ROOMS
  
 4. A120A AND OTHER SHEETS, WOMENS WC 471, DOOR 471.3
 APPEARS TO OBSTRUCT THE MANEUVERING CLEARANCE FOR DOOR
 471.2, REVISE, FBC A 404.2.4.
  
 5. IT APPEARS THAT THERE IS AN ADDITION OF SQUARE FOOT
 AREA. REVISE PLAN TO CLARIFY OLD TOTAL, NEW TOTAL.
 BUILDING DATA NEEDS TO BE UPDATED, BOTH ON THE PLAN AND
 IN OUR SYSTEM FOR RECORDKEEPING AND CO, AND ADDITIONAL
 IMPACT FEES MAY BE DUE. SEE IMPACT FEE REVIEW.
  
 6. THE ARCHITECTURAL SHEETS HAVE AN ERROR THAT
 "CERTIFICATION IS INVALID", BUT THE SIGNATURE SHOWS
 THAT IT WAS SIGNED BY WILLIAM HOBBS. PLEASE CONTACT
 ISSUER AND PROVIDE INFORMATION REGARDING THIS ERROR.
 PLEASE DO NOT UPLOAD NEW SHEETS UNLESS THEY ARE REVISED
 TO ADDRESS PLAN REVIEW COMMENTS, OR IF THE ISSUER OF
 DIGITAL SEAL/SIGNATURE ADVISES THAT SHEETS NEED TO BE
 RE-SIGNED/SEALED. FAC61G15-30, FS481.
  
 7. D3-A422 (AND POSSIBLY OTHER LOCATIONS) SPECS PT
 PLYWOOD. THIS IS A TYPE II BUILDING; SEE FBC B 603.1.
 IF DOR FEELS THIS FALLS UNDER AN EXCEPTION, REVISE
 DETAIL TO INCLUDE EXCEPTION AND SQUARE FOOT AREA
 AFFECTED. SEND VIA EMAIL FOR PRELIMINARY REVIEW AND
 ACCEPTANCE PRIOR TO RESUBMITTAL.
  
 8. MANY SHEETS REVIEWED APPEAR TO AFFECT OTHER PERMITS.
 FOR INSTANCE, THE HARDSCAPE REVIEWED UNDER THIS
 REVISION APPEARS TO AFFECT THE HARDSCAPE PERMIT
 16010525. AFTER THIS REVISION IS REVIEWED, COORDINATE
 WITH STEVE KENNEDY (OR WITH ME IF HE IS NOT AVAILABLE)
 TO HAVE THE OTHER PERMITS UPDATED. ADDITIONAL REVISIONS
 ARE NOT REQUIRED.
  
 9. PRIOR TO RESUBMITTAL, OR SUBMITTAL OF OTHER PERMITS
 AND/OR REVISIONS, CONTACT STEVE KENNEDY TO COORDINATE
 FEES.
  