| 2017-05-12 07:40:39 | ****PROVISO**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17020058 |
| | ADD: 550 OKEECHOBEE BLVD. SUITE # CU-2 |
| | CONT: BRANCH CONSTRUCTION |
| | TEL: 561-833-6206 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | SHEET 02-A SHOWS THE BREAKROOM DOOR # 06 DOES NOT |
| | COMPLY WITH 2014 ACCESS. CODE 404.2.4 MANEUVERING |
| | CLEARANCES. MINIMUM MANEUVERING CLEARANCES AT DOORS AND |
| | GATES SHALL COMPLY WITH 404.2.4. MANEUVERING CLEARANCES |
| | SHALL EXTEND THE FULL WIDTH OF THE DOORWAY AND THE |
| | REQUIRED LATCH SIDE OR HINGE SIDE CLEARANCE. |
| | |
| | 3RD REVIEW - APPLICANT HAS PROPOSED A RESOLUTION VIA |
| | EMAIL. THIS PERMIT IS ISSUED WITH PROVISO - REVISE |
| | SHEET 03-A AND OTHER AFFECTED SHEETS, BREAK ROOM 05 |
| | DOOR TO COMPLY WITH FBC A 404.2.4 PRIOR TO FINAL |
| | INSPECTION. |
| | |
| | |