| Plan Review Notes For Permit 17020058 |
| Permit Number |
17020058 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-02-15 15:54:59 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. THE TOILET PAPER DISPENSER SHOW 0'-8' OFF THE FRONT | | | OF TOILET IT SHALL BE 7 "- 9" MAXIMUM IN FRONT OF THE | | | WATER CLOSET MEASURED TO THE CENTERLINE OF THE | | | DISPENSER. PER 604.7 | | | | | | 2. GRAB BARS SHALL BE MEASURED FROM FINISHED FLOOR TO | | | TOP OF THE GRIPPING SURFACE. PER FBC ACC 609.4 | | | | | | 3. SHOW CLEARANCE AROUND A WATER CLOSET SHALL BE 60 | | | INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE | | | WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM | | | THE REAR WALL. PER FBC ACC 604.3.1 | | | | | | 4. SHOW CLEAR FLOOR SPACE FOR LAV 30" X 48". PER FBC | | | ACC 606.2 | | | | | | 5. SHT P-2 THE DETAIL FOR THE WATER HEATER SHOWS T+P | | | DRAIN AND PAN DRAIN TERMINATING ABOVE A MOP SINK THERE | | | IS NO MOP SINK SHOWN ON PLAN PLEASE CLARIFY. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND | | | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON | | | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|