| Plan Review Notes For Permit 17020058 |
| Permit Number |
17020058 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-02-06 12:55:06 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17020058 | | | 2/6/17 | | | | | | 1) PROVIDE A DUCT SMOKE DETECTOR IN THE RETURN AIR | | | SYSTEM OF THE NEW HEAT PUMP- SECTION 606.2.1. | | | | | | 2) PROVIDE AN AUTOMATIC SHUTOFF DAMPER FOR THE O/A | | | INTAKE DUCT- SECTION C403.2.4.4 FBC-14 ENERGY | | | CONSERVATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|