| Date |
Text |
| 2017-02-09 10:12:04 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET O2 A - THE RESTROOM DOOR OPENS INTO THE EXIT |
| | CORRIDOR. |
| | |
| | PER NFPA 101 CHAPTER 7, MEANS OF EGRESS |
| | 7.2.1.4.3 DOOR LEAF ENCROACHMENT |
| | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE |
| | REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, |
| | OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT |
| | MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A |
| | CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, |
| | UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| | EXISTING BUILDING. |
| | (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS |
| | PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED |
| | WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY |
| | OPEN. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 2) SHEET O2 A - THERE IS A PIECE OF FURNITURE LOCATED |
| | IN FRONT OF A SET OF DOUBLE DOORS THAT ARE INDICATED AS |
| | OPEN. THOUGH THE OTHER SET OF DOORS ARE INDICATED AS |
| | THE EXIT DOORS, PLEASE INDICATE IF THESE WILL BE LOCKED |
| | AND CLEARLY MARKED AS NOT EXIT DOORS. |
| | |
| | PLEASE REVIEW, CLARIFY AAAAAND CORRECT. |
| | |
| | |
| | |
| | |
| | 3) SHEET O3 A - THERE IS AN EXIT SIGN IN THE CORRIDOR |
| | LEADING INTO TREATMENT ROOM 7; HOWEVER, THERE IS NO |
| | EXIT SIGN INDICATED ON SHEET E 1. |
| | |
| | HOWEVER, PER NFPA 101, CHAPTER 7, MEANS OF EGRESS - |
| | 7.5.2 IMPEDIMENTS TO EGRESS. SEE ALSO 7.1.9 AND |
| | 7.2.1.5. |
| | 7.5.2.1* ACCESS TO AN EXIT SHALL NOT BE THROUGH |
| | KITCHENS, STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS |
| | 36 AND 37, RESTROOMS, WORKROOMS, CLOSETS, BEDROOMS OR |
| | SIMILAR SPACES, OR OTHER ROOMS OR SPACES SUBJECT TO |
| | LOCKING, UNLESS PASSAGE THROUGH SUCH ROOMS OR SPACES IS |
| | PERMITTED FOR THE OCCUPANCY BY CHAPTER18, 19, 22, OR |
| | 23. |
| | |
| | TREATMENT ROOM 7 DOOR CAN NOT BE MARKED AS AN EXIT. |
| | |
| | PLEASE CORRECT SHEET O3 A AND ENSURE AN EXIT SIGN IS |
| | NOT PALCED ABOVE THAT DOOR. |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |