| 2017-02-03 16:13:32 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17020058 |
| | ADD: 550 OKEECHOBEE BLVD. SUITE # CU-2 |
| | CONT: BRANCH CONSTRUCTION |
| | TEL: 561-833-6206 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. FEB. 03/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) SHEET 01-A THE COVERSHEET LIST THIS BUILDING AS A |
| | BUILDING TYPE III-B. PLEASE NOTE THIS IS A 20 STORY |
| | HIGH RISE BUILDING. PLEASE CORRECT TO A MINIMUM |
| | BUILDING TYPE I-A CONSTRUCTION, SEE 2014 FBC-B TABLE |
| | 503. |
| | |
| | 2) SHEET 01-A THE COVERSHEET ALSO LIST THE OCCUPANCY |
| | TYPE AS A-2 ASSEMBLY AND B OCCUPANCY. THE OCCUPANCY |
| | TYPE PER SECTION 304.1 IS A B/ BUSINESS OCCUPANCY. |
| | |
| | 3) SHEET 01-A THE COVERSHEET ALSO LIST THE BUILDING |
| | FIRE PROTECTION AS UNPROTECTED / SPRINKLERED NEW |
| | SYSTEM. PLEASE PROVIDE THE MEANING OF UNPROTECTED. IN |
| | THE 2014 FBC-B TABLE 601 THE BUILDING ELEMENT TABLE |
| | REQUIRES ALL STRUCTURAL ELEMENTS TO BE FIRE RATED IN |
| | HOURS. |
| | |
| | 4) SHEET 01-A THE COVERSHEET ALSO LIST THE OCCUPANT |
| | LOAD AS 10 IN THE UPPER RIGHT HAND CORNER OF THE SHEET, |
| | BUT IN THE LOWER RIGHT CORNER OF THE SHEET THE HEADING |
| | OF BUILDING DATA AND A/C CALCULATIONS BOTH INDICATE THE |
| | SQUARE FOOTAGE OF THE TENANT SPACE AS 1,182 SQUARE |
| | FEET. 1,182/100= 12 OCCUPANTS TABLE 1004.1.2. |
| | |
| | 5) SHEET 02-A SHOWS THE BREAKROOM DOOR # 06 DOES NOT |
| | COMPLY WITH 2014 ACCESS. CODE 404.2.4 MANEUVERING |
| | CLEARANCES. MINIMUM MANEUVERING CLEARANCES AT DOORS AND |
| | GATES SHALL COMPLY WITH 404.2.4. MANEUVERING CLEARANCES |
| | SHALL EXTEND THE FULL WIDTH OF THE DOORWAY AND THE |
| | REQUIRED LATCH SIDE OR HINGE SIDE CLEARANCE. |
| | |
| | 6) SHEET 02/A DOES NOT SHOW COMPLIANCE FOR THE BREAK |
| | ROOM SINK, COMPLIANCE WITH 2014 ACCESS. CODE |
| | 606.3 HEIGHT. |
| | 606.2 CLEAR FLOOR SPACE. |
| | 606.4 FAUCETS. |
| | 606.5 EXPOSED PIPES AND SURFACES. |
| | |
| | 7) SHEET 02/A THE RECEPTION DESK DOES NOT INDICATE |
| | COMPLIANCE WITH 2014 FBC-ACCESS. CODE 902.3 HEIGHT. THE |
| | TOPS WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 |
| | INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |