| 2018-02-15 12:17:41 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. ESTIMATED AIC CALCULATIONS ARE NOT ACCEPTABLE. |
| | PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. WE |
| | WILL ACCEPT THIS AS A DEFERRED SUBMITTAL WITH THE |
| | UNDERSTANDING THAT THIS WILL BE PROVIDED PRIOR TO |
| | INSPECTION SO THE INSPECTOR CAN VERIFY EQUIPMENT IS |
| | PROPERLY SIZED AND LABELED. NEC 110.9, 110.10 |
| | 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS FOR THE MAIN SERVICE. IF FOR FUTURE TENANTS, |
| | PROVIDE BASIS FOR SIZE OF SERVICE BASED ON SQUARE |
| | FOOTAGE DEMANDS EXPECTED. NEC 220, 215.2 |
| | 3. IS THE EXISTING SERVICE WIRE THE SAME AS PROPOSED IN |
| | THE NEW SERVICE MAST BEING ADDED? PROVIDE |
| | CLARIFICATION. NEC 310.10(H)(2) |
| | 4. CIRCUIT HP2-4 IS SHOWN IN PANEL SCHEDULE AS THE EWC, |
| | BUT IT IS SHOWN ON PLAN AS LIGHTING CIRCUIT. EWC MUST |
| | HAVE A DEDICATED CIRCUIT THAT IS GFCI PROTECTED. |
| | PROVIDE CORRECTION. NEC 422.52 |
| | 5. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED |
| | FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE |
| | CORRECTION. NEC 700.12(F) |
| | |
| | ALSO, THERE ARE PREVIOUS COMMENTS NOT ADDRESSED: |
| | FURTHER COMMENTS IN PARENTHESES. |
| | |
| | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | 1. PLEASE NOTE THAT A NEW ELEVATOR IS INDICATED ON |
| | APPLICATION, SHOW ALL NEW LOADS FOR ELEVATOR REFLECTED |
| | ON PANEL SCHEDULE ASSIGNED. COMPLY WITH ALL NEC 620.24 |
| | BRANCH CIRCUIT HOIST WAY PIT, SUMP, LIGHTING, |
| | RECEPTACLE ETC. 620.51 DISCONNECTING MEANS AND CONTROLS |
| | (A-D) AND PART8- CONTROL SPACES ETC. (PROVIDE NOTE THAT |
| | ELEVATOR WILL BE UNDER SEPARATE PERMIT.) |
| | 2. (ADDRESSED, BUT NEEDS CORRECTIONS. SEE COMMENT 3 |
| | ABOVE.) |
| | 3. PROVIDE A NOTE THAT NO ELECTRICAL THAT IS NOT PART |
| | OF THE STAIRWELL CAN PASS THRU THE AREA. FBC 107.3.5 |
| | (DID NOT SEE NOTE ON PLAN.) |
| | 4. ADDRESSED. |
| | 5. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO |
| | INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC |
| | 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE |
| | VERBIAGE IN CODE. (NEED TO QUOTE BOTH CODE SECTIONS ON |
| | PLAN FOR DIFFERENT TYPE OF LABELS REQUIRED.) |
| | 6. SHOW PER FBC EC 405- THE AUTOMATIC MEANS OF LIGHTING |
| | CONTROLS PER ENERGY CODE AND COMPLIANCE WITH LIGHTING |
| | DENSITIES. (DID NOT COMPLY) |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |