| 2017-02-09 10:20:55 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17011234 | | | 2/9/17 | | | | | | 1) DUCT SMOKE DETECTORS, FIRE DAMPERS, AND A FIRE RATED | | | CEILING ARE CALLED OUT IN THE DESIGN TABLE ON SHEET | | | M.2. PLEASE SHOW THEIR LOCATIONS WITH SYMBOLS ON SHEET | | | M.1 OR REVISE THE TABLE TO MATCH THE PLANS. | | | | | | 2) THE 4X12 RETURN DUCTS RETURNING 200 CFMS OF AIR ARE | | | UNDERSIZED BASED ON A FRICTION RATE OF 0.094. PLEASE | | | INCREASE THE SIZE OF THE DUCTS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|