2017-02-03 08:06:411ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #17011234
 2/3/17
  
 1) SHEET M.1: SOME OF THE PRINT ON THE PLANS NEEDS TO
 BE BOLDER FOR REVIEW AND FOR SCANNING TO PUBLIC
 RECORDS- SECTION 107.2.1 WPB AMENDMENTS TO THE FBC.
 PLEASE PROVIDE BOLDER PRINT FOR THE DUCT SIZES,
 DIFFUSER AND GRILL SIZES, AND CFM CAPACITIES.
  
 2) M.1: PROVIDE THE SUPPLY DUCT SIZES AT OFFICES 104 &
 107.
  
 3) INDICATE THE TYPE OF DUCT INSULATION TO BE INSTALLED
 AND R-VALUE.
  
 4) THE PROJECT HAS BEEN CLASSIFIED AS A LEVEL 2
 ALTERATION. REFER TO SECTION 809.2 FBC-14 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3
 FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES
 THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 5) SHOW THE O/A DUCTS SUPPLYING THE TWO AHU'S AND
 INDICATE COMPLIANCE WITH SECTION C403.2.4.4 FBC-14
 ENERGY CONSERVATION- AUTOMATIC DAMPERS FOR O/A
 SHUTDOWN.
  