| Plan Review Notes For Permit 17011234 |
| Permit Number |
17011234 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-02-03 08:06:41 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES | | | PERMIT #17011234 | | | 2/3/17 | | | | | | 1) SHEET M.1: SOME OF THE PRINT ON THE PLANS NEEDS TO | | | BE BOLDER FOR REVIEW AND FOR SCANNING TO PUBLIC | | | RECORDS- SECTION 107.2.1 WPB AMENDMENTS TO THE FBC. | | | PLEASE PROVIDE BOLDER PRINT FOR THE DUCT SIZES, | | | DIFFUSER AND GRILL SIZES, AND CFM CAPACITIES. | | | | | | 2) M.1: PROVIDE THE SUPPLY DUCT SIZES AT OFFICES 104 & | | | 107. | | | | | | 3) INDICATE THE TYPE OF DUCT INSULATION TO BE INSTALLED | | | AND R-VALUE. | | | | | | 4) THE PROJECT HAS BEEN CLASSIFIED AS A LEVEL 2 | | | ALTERATION. REFER TO SECTION 809.2 FBC-14 EXISTING | | | BUILDING CODE AND PROVIDE MINIMUM VENTILATION | | | CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3 | | | FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES | | | THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR. | | | | | | 5) SHOW THE O/A DUCTS SUPPLYING THE TWO AHU'S AND | | | INDICATE COMPLIANCE WITH SECTION C403.2.4.4 FBC-14 | | | ENERGY CONSERVATION- AUTOMATIC DAMPERS FOR O/A | | | SHUTDOWN. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|