| 2017-02-06 09:37:56 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: |
| | JOB ADDRESS: 2508 N. AUSTRALIAN AVE. |
| | DESCRIPTION: INTERIOR BUILDING OF OFFICES |
| | MASTER PERMIT: 17011234 |
| | |
| | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| | SUBMITTED CORRECTIONS. |
| | |
| | 1. FBC-EC405.5.2 INTERIOR LIGHTING POWER ALLOWANCE. THE |
| | TOTAL INTERIOR POWER ALLOWANCE IS DETERMINED ACCORDING |
| | TO THE APPLICABLE TABLES AS INDICATED IN THIS SECTION. |
| | PPROVIDE A FIXTURE SCHEDULES TO INDICATE COMPLIANCE. |
| | 2. FBC EC405.2.2.2 OCCUPANCY SENSORS. OCCUPANCY SENSORS |
| | SHALL BE INSTALLED IN ALL CLASSROOMS, |
| | CONFERENCE/MEETING ROOMS, EMPLOYEE LUNCH AND BREAK |
| | ROOMS, PRIVATE OFFICES, RESTROOMS, STORAGE ROOMS AND |
| | JANITORIAL CLOSETS, AND OTHER SPACES 300 SQUARE FEET |
| | (28 M2) OR LESS ENCLOSED BY FLOOR-TO-CEILING HEIGHT |
| | PARTITIONS. THESE AUTOMATIC CONTROL DEVICES SHALL BE |
| | INSTALLED TO AUTOMATICALLY TURN OFF LIGHTS WITHIN 30 |
| | MINUTES OF ALL OCCUPANTS LEAVING THE SPACE, AND SHALL |
| | EITHER BE MANUAL ON OR SHALL BE CONTROLLED TO |
| | AUTOMATICALLY TURN THE LIGHTING ON TO NOT MORE THAN 50 |
| | PERCENT POWER. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |