Plan Review Notes
Plan Review Notes For Permit 17011234
Permit Number 17011234
Review Stop B
Sequence Number 1
Notes
Date Text
2017-02-03 14:07:51BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17011234
 ADD: 2508 N AUSTRALIAN AVE. SUITE # ?????
 CONT: JERRET CONSTRUCTION VERSES WINDOW MASTERS OF S.
 FLORIDA
 TEL: 954-520-8095
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. FEB. 03/2017
 ACTION: DENIED
  
 1) THE QUALIFIER JERROLD GROSS IS REGISTERED UNDER
 WINDOW MASTERS OF S. FLORIDA IN THE CITY OF WEST PALM
 BEACH. YOU WILL NEED TO REGISTER THE COMPANY JERRET
 CONSTRUCTION CO. INC. AS WELL. A HOLD WILL BE PUT ON
 THIS PERMIT NO TO ISSUE UNTIL A NEW REGISTRATION
 OCCURS.
  
 2) THE PLANS DO NOT INDICATE IF THIS IS A SINGLE TENANT
 OR MULTIPLE TENANTS. THE PLANS ONLY SHOW WHERE WORK IS
 OCCURRING IN THE WEST ? OF THE BUILDING. SHEET AB.1
 DOES SHOW WORK IN THE SHARED CORRIDOR IF THIS IS
 MULTIPLE TENANTS WITHIN THE BUILDING .
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
 WITH THE TOTAL SQ. FT. OF THE BUILDING BEING 5,000 SQ.
 FT. THE OCCUPANT LOAD WOULD BE 50 FOR THE TOTAL
 BUILDING, EVEN IF THERE IS ONLY ONE TENANT.
 IN THE 2014 FBC-B TABLE 1018.1 WILL REQUIRE A 1 HOUR
 FIRE RATED CORRIDOR (BUILDING NOT FIRE SPRINKLERED)
 WHEN THE OCCUPANT LOAD IS MORE THAN 30 WITH OPENING
 PROTECTIVES PER FBC-B TABLE 716.5 DOORS ARE REQUIRED TO
 BE 20 MINUTE.
  
 3) SHEET LS.1 THE FORMULA FOR EXITING OUT BOTH EXIT A
 &B 34?/0.2= 170 OCCUPANTS NOT 167. 2014 FBC-B 1005.3.2.
  
 4) THE LIFE SAFETY PLAN NOR SHEET A1 SHOW COMPLIANCE
 WITH 2014 FBC-B 906.1 PORTABLE FIRE EXTINGUISHERS.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
  