| 2017-03-10 08:46:03 | RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW |
| | COMMENTS. |
| | CODE: FBC 5TH EDITION (2014) |
| | |
| | 1- EQUIPMENT SIZING CALCULATIONS SUBMITTED: |
| | A) THE DESIGN INFORMATION OF THE PROJECT SUMMARY |
| | CALCULATIONS SUBMITTED SPECIFIES MIAMI INTERNATIONAL |
| | AIRPORT. THIS IS NOT THE CORRECT LOCATION FOR THIS |
| | HOUSE. REVISE AS REQUIRED. SEC. R403.6 FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | |
| | B) ONLY THE PROJECT SUMMARY SHEET WAS SUBMITTED. |
| | PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS FOR THE |
| | ACTUAL ORIENTATION OF THE BUILDING AS REQUIRED BY SEC. |
| | R403.6 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | NOTE: SEE SURVEY FOR CORRECT HOUSE ORIENTATION. ALSO, |
| | COORDINATE EQUIPMENT SIZING CALCULATIONS WITH THE |
| | REQUIRED REVISED ENERGY CALCULATIONS. |
| | |
| | C) ENGINEER WHO PREPARED THE ENERGY CALCULATIONS TO |
| | PROVIDE HIS INFORMATION AS REQUIRED BY FAC 61G15-23.002 |
| | WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS. |
| | |
| | 2- TRANSFER DUCT SIZE SPECIFIED ON SHEET M-1 FOR THE |
| | MASTER BEDROOM DOESN'T COMPLY WITH THE BALANCED RETURN |
| | AIR SEC. M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | DUCT NEEDS TO BE SIZED BASED ON ALL THE SUPPLY AIR |
| | GOING INTO THE MASTER BEDROOM. SEE EXCEPTION #3 ON SEC. |
| | M1602.4. REVISE AS REQUIRED. |
| | |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| | FOR REFERENCE. |
| | |