Plan Review Notes
Plan Review Notes For Permit 17011210
Permit Number 17011210
Review Stop B
Sequence Number 1
Notes
Date Text
2017-03-08 19:00:36RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014)
  
 1- ALTERATION LEVEL SPECIFIED ON SHEET T-1 UNDER THE
 DESIGN CRITERIA IS INCORRECT. ACCORDING TO THE SCOPE OF
 WORK SHOWN ON PLAN SUBMITTED, THIS IS ALTERATION LEVEL
 3 NOT 2. REVISE AS REQUIRED. SEC. 505 FBC-EXISTING
 BUILDING, 5TH EDITION (2014).
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW BASED ON ALL THE SCOPE OF WORK SHOWN ON PLANS.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND ALL DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. PROVIDE COPY OF
 SIGNED CONTRACT THAT INCLUDES ALL THE SCOPE OF WORK.
  
 3- SPECIFY SELF CLOSING DEVICE FOR GARAGE DOOR LEADING
 TO THE FAMILY ROOM AREA AS REQUIRED BY SEC. R302.5.1
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 4- REVISE ENERGY CALCULATIONS FORM R405-2014 SUBMITTED;
 A) INFORMATION ON TOP OF FORM SUBMITTED IS INCORRECT.
 PROVIDE THE CORRECT OWNER AND BUILDER NAME. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 B) ITEM #1 IS INCORRECT. THIS IS NOT NEW CONSTRUCTION.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 C) NUMBER OF BEDROOMS SPECIFIED ON ITEM #4 IS
 INCORRECT. REVISE AS REQUIRED TO MATCH PROPOSED PLANS.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 D) PROVIDE THE INFORMATION FOR THE HOT WATER ON ITEM
 #14. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 E) ENGINEER WHO PREPARED THE ENERGY CALCULATIONS TO
 PROVIDE HIS INFORMATION AS REQUIRED BY FAC 61G15-23.002
 WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS.
  
 F) ROOF INFORMATION ON PAGE 3 OF 5 IS INCORRECT. THIS
 HOUSE DOESN'T HAVE SHINGLES. REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 G) ATTIC INFORMATION ON PAGE 3 OF 5 SPECIFIES 1/300
 VENT RATIO. THE MINIMUM VENT RATIO REQUIRED BY SEC.
 R806.2 FBC-RESIDENTIAL IS 1/150. PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS SHOWING HOW THE EXISTING
 HOUSE COMPLIES WITH THE 1/300 VENT RATIO AS REQUIRED BY
 THE EXCEPTION OF SEC. R806.2. OTHERWISE REVISE THE
 SPECIFIED VENT RATIO.
  
 H) THE ORIENTATION OF THE WALLS AND WINDOWS DON'T MATCH
 ACTUAL BUILDING ORIENTATION. REVISE AS REQUIRED TO
 MATCH THE ACTUAL ORIENTATION OF THE BUILDING. SEE
 SURVEY AND REVISE AS REQUIRED. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 I) REVISE THE WINDOWS OVERHANG DEPTH ON PAGE 4 OF 5 TO
 MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 J) BUILDER TO COMPLETE THE EPL DISPLAY CARD AS REQUIRED
 BY SEC. R405.4.3 FBC-ENERGY CONSERVATION.
  
 5- A) IT'S NOT CLEAR WHICH WINDOWS ARE GOING TO BE
 REPLACED. CLARIFY WHY SUBMITTING NOA 16-0714.06 FOR
 SINGLE HUNG WINDOWS?. CLEARLY SPECIFY ON PLANS WHICH
 DOORS AND WINDOWS ARE GOING TO BE REPLACED. SEC.
 107.2.1 CITY AMENDMENTS. NOTE: WINDOW "G" FOR PROPOSED
 BEDROOM #2 DOESN'T SEEM TO COMPLY WITH THE EGRESS
 REQUIREMENTS. CLARIFY IF THIS WINDOW IS GOING TO BE
 REPLACED. IF SO, THEN SPECIFY TYPE AND SIZE OF EXISTING
 WINDOW AND TYPE AND SIZE OF PROPOSED WINDOW TO VERIFY
 COMPLIANCE WITH SEC 704 FBC-EXISTING BUILDING, 5TH
 EDITION (2014).
  
 B) NOA 16-0218.03 SUBMITTED FOR MULLIONS. PLANS DON'T
 SHOW ANY WINDOW AND MULLION REPLACEMENT. CLARIFY WHERE
 IS THE HIGHLIGHTED MULLION SIZE SHOWN ON SHEET 5 OF 25
 GOING TO BE INSTALLED. SEC. 107.2.1 CITY AMENDMENTS.
 COORDINATE WITH ITEM #5(A) ABOVE.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) INSWING ENTRY DOORS AS SHOWN ON PROPOSED PLAN
 SUBMITTED. NOA 16-0629.16 SUBMITTED IS FOR "OUTSWING"
 DOORS ONLY.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]