| 2017-05-10 14:55:15 | RESIDENTIAL (R3) ADDITION, SECOND BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO ONCE THE |
| | ENERGY CALCULATIONS ARE SIGNED BY THE OWNER AND THE |
| | COUNTY IMPACT FEES ARE PAID. PROVISO MEANS THAT OWNER |
| | MAY PROVIDE THE REQUIRED INFORMATION AFTER THE PERMIT |
| | IS ISSUED AND BEFORE INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. REVISION FEES MAY APPLY. |
| | OWNER/BUILDER TO ADVICE IN WRITING ( RESPONDING TO THIS |
| | E-MAIL) IF PROVISO OPTION IS PREFERRED AT THIS TIME. |
| | |
| | |
| | 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) |
| | FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED |
| | PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY |
| | IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT |
| | CODE. |
| | |
| | 2- ENERGY CALCULATIONS SUBMITTED: |
| | A) OWNER TO CERTIFY COMPLIANCE AT THE BOTTOM OF THE |
| | FORM AS REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | |
| | B) PROVIDE THE NAME OF THE PERSON COMPLETING THE |
| | CALCULATIONS A REQUIRED BY SEC. R405.4.2 FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | |
| | C) PROVIDE CORRECT INFORMATION ON TOP OF FORM. ON |
| | TARGET IS NOT THE BUILDER. REVISE AS REQUIRED BY SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | D) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| | (EPL) DISPLAY CARD AS REQUIRED BY SEC. R405.4.3 |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) NEW ROOF RIDGE VENTS AS SPECIFIED ON PLANS. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL. |
| | |
| | B) EXTERIOR DOORS AS SHOWN ON PLANS. |
| | RESPONSE: PROVIDE FLORIDA PRODUCT APPROVAL COVER SHEET |
| | THAT CORRESPONDS TO DRAWINGS SUBMITTED AND PROVIDE |
| | COMPLETE AND CLEAR DRAWINGS. DRAWINGS SUBMITTED ARE CUT |
| | OFF. NEED COMPLETE DRAWINGS. UNCUT DRAWINGS. |
| | |
| | C) SINGLE HUNG WINDOWS AS SHOWN ON PLANS. |
| | RESPONSE: PROVIDE FLORIDA PRODUCT APPROVAL COVER SHEET |
| | THAT CORRESPONDS TO DRAWINGS SUBMITTED AND PROVIDE |
| | COMPLETE AND CLEAR DRAWINGS. DRAWINGS SUBMITTED ARE CUT |
| | OFF. NEED COMPLETE DRAWINGS. UNCUT DRAWINGS. |
| | |
| | 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE INSERT ANY REVISED SHEET AND REMOVE OLD |
| | SHEETS. DON'T STAPLE OLD SHEETS. SUBMIT OLD SHEETS FOR |
| | REFERENCE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |