| Plan Review Notes For Permit 17011189 |
| Permit Number |
17011189 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-01 14:30:13 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) | | | SHEET G1.001 - ADDED COMMENT # 32, 33 & 34 | | | | | | 32. ALL FIRE ALARM AND FIRE SPRINKLER WORK SHALL BE | | | DONE UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE | | | SAFETY CONTRACTORS. | | | | | | 33. ALL FIRE ALARM AND FIRE SPRINKLERS SYSTEMS SHALL BE | | | MAINTAINED THROUGHOUT CONSTRUCTION. | | | | | | 34. ALL EXITS SHALL BE MAINTAINED AND FUNCTIONAL | | | THROUGHTOUT CONSTRUCTION ACTIVITY OR A LIFE SAFETY PLAN | | | SHALL BE SUBMITTED FOR APPROVAL. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|