| 2017-03-28 10:20:01 | APPROVED WITH PROVISO TO BE CORRECTED UNDER MASTER | | | PERMIT 17011176 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. WILL THE SINGLE USER BATHROOM NEXT TO THE RETAIL | | | SPACE BE ACCESSIBLE FOR THE OCCUPANTS OF THE RETAIL | | | SPACE TO USE, IT APPEARS THAT IT CAN ONLY BE ACCESSED | | | THROUGH THE STORAGE FACILITY PLEASE CLARIFY. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 2. THE COFFEE BAR SHALL COMPLY WITH FBC ACC | | | 902.2,902.3, 308 | | | | | | 5. A CLEAN OUT IS REQUIRED AT THE BASE OF ANY WASTE OR | | | SOIL STACK. PER FBC PL 708.3.4 | | | | | | 7. TEMPERED WATER IS REQUIRE AT ALL LAVATORY'S IN | | | PUBLIC BATHROOMS. PER FBC PL 416.5 | | | | | | 8.SHOW THE REQUIRED TRAP PRIMERS ON ALL FLOOR DRAINS. | | | PER FBC PL 1002.4 | | | | | | 9. A SEPARATE SHUT OFF FOR EACH HOSE BIB IS REQUIRED. | | | PER FBC PL 606.2(2) | | | | | | | | | | | | |
|