| 2017-05-25 14:56:11 | FAILED |
| | |
| | PROVIDE WRITTEN RESPONSES. |
| | |
| | 1) REPEAT UPDATED COMMENT: FOUNDATION SHEET S1.1 DOES |
| | NOT SHOW THE RELOCATED DOOR LOCATION THAT IS REFLECTED |
| | ON THE REMAINDER OF THE PLANS. ALL PLANS SHALL SHOW THE |
| | SAME CONDITIONS. THE STRUCTURAL PLAN MUST BE CORRECTED |
| | PRIOR TO ZONING APPROVAL OF THIS BUILDING PERMIT. THE |
| | SITE AND CIVIL PLANS SHALL BE CORRECTED PRIOR TO C.O. |
| | (SEE COMMENT NO. 3 BELOW). |
| | |
| | 2) REPEAT COMMENT: THE FIRST FLOOR ELECTRICAL SITE |
| | PLANS SHOW HEAT PUMPS (HP-5 AND HP-7) ON THE SOUTH SIDE |
| | OF THE BUILDING. MECHANICAL EQUIPMENT IS NOT PERMITTED |
| | BETWEEN THE BUILDING AND CONGRESS AVENUE. SHEET M1.1 |
| | CORRECTLY SHOWS BOTH OF THESE UNITS TO THE REAR OF THE |
| | BUILDING. |
| | |
| | 3) THERE ARE DOORS SHOWN ON VARIOUS PLANS IN NEW |
| | LOCATIONS AND THERE ARE MORE HEAT PUMPS (MECHANICAL |
| | EQUIPMENT) SHOWN ALONG THE REAR OF THE BUILDING AS |
| | COMPARED TO THE SITE, LANDSCAPE, ELEVATION AND CIVIL |
| | PLANS APPROVED AS PART OF THE PLANNING APPROVAL |
| | PROCESS. SINCE THESE PLANS HAVE CHANGED, PRIOR TO C.O. |
| | OF THIS BUILDING, AN AS BUILT MINOR AMENDMENT IS |
| | REQUIRED TO BE SUBMITTED TO THE PLANNING DIVISION. |
| | |
| | 4) REPEAT COMMENT: IN ACCORDANCE WITH RESOLUTION NO. |
| | 201-16, WHICH APPROVED THIS SITE DEVELOPMENT, PRIOR TO |
| | ZONING APPROVAL OF THIS BUILDING PERMIT PROVIDE THE |
| | PLANNING DIVISION WITH A COPY OF THE APPROVED DRIVEWAY |
| | CONNECTION PERMIT FROM PALM BEACH COUNTY ENGINEERING |
| | FOR THE DRIVEWAY CONNECTIONS TO NORTH CONGRESS AVENUE. |
| | |
| | 5) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR THE |
| | FOLLOWING: |
| | |
| | A. SIGNAGE |
| | B. LANDSCAPE |
| | C. IRRIGATION |
| | D. SITE LIGHTING |
| | E. PARKING LOT STRIPING |
| | |
| | CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
| | [email protected] |
| | |