| Plan Review Notes For Permit 17011176 |
| Permit Number |
17011176 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-05-04 07:21:20 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17011176 | | | 5/4/17 | | | | | | 1) THE AC CALCULATIONS FOR THE FC-6 INDICATE THE UNIT | | | IS OVERSIZED. THE CALCULATION INDICATES 2.2 TONS OF | | | COOLING REQUIRED- THE SCHEDULE SHOWS FC-6 IS A 5-TON | | | UNIT- SEE SECTION C403.2.2 FBC-14 ENERGY CONSERVATION. | | | PLEASE NOTE THAT THE FC-6 CALULATION IS LABELED AS | | | "OFFICE" HOWEVER THE UNIT APPEARS TO BE LOCATED IN THE | | | STORAGE AREA. | | | | | | 2) THE AC CALCS ARE INDICTING FC-7 TO BE LOCATED ON THE | | | 2ND FLOOR, HOWEVER THE PLAN SHOWS IT ON THE 1ST FLOOR. | | | | | | 3) THE DUCT SMOKE DETECTORS FOR THE HEAT PUMPS SHALL BE | | | LIOCATED UPSTREAM OF THE OUTSIDE AIR DUCT CONNECTION- | | | SEE SECTION 606.2.1 AND CORRECT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|