Plan Review Notes
Plan Review Notes For Permit 17011176
Permit Number 17011176
Review Stop M
Sequence Number 3
Notes
Date Text
2017-05-04 07:21:201ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17011176
 5/4/17
  
 1) THE AC CALCULATIONS FOR THE FC-6 INDICATE THE UNIT
 IS OVERSIZED. THE CALCULATION INDICATES 2.2 TONS OF
 COOLING REQUIRED- THE SCHEDULE SHOWS FC-6 IS A 5-TON
 UNIT- SEE SECTION C403.2.2 FBC-14 ENERGY CONSERVATION.
 PLEASE NOTE THAT THE FC-6 CALULATION IS LABELED AS
 "OFFICE" HOWEVER THE UNIT APPEARS TO BE LOCATED IN THE
 STORAGE AREA.
  
 2) THE AC CALCS ARE INDICTING FC-7 TO BE LOCATED ON THE
 2ND FLOOR, HOWEVER THE PLAN SHOWS IT ON THE 1ST FLOOR.
  
 3) THE DUCT SMOKE DETECTORS FOR THE HEAT PUMPS SHALL BE
 LIOCATED UPSTREAM OF THE OUTSIDE AIR DUCT CONNECTION-
 SEE SECTION 606.2.1 AND CORRECT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  