2017-05-31 09:00:38 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17011176 (BUILDING PERMIT)
 ADD: 1620 N. CONGRESS AVE.
 CONT: BRICKELL GROUP
 TEL: 305-370-3988
 TEL: 561-373-3902 / KARI
 E-MAIL: [email protected]
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 3RD REVIEW
 DATE: TUES. MAY 30, 2017
 ACTION: DENIED
  
 1) BUILDING PROVISO: NOTICE ONLY, 111 110.3.7.4.3 ALL
 SHORING AND RESHORING PROCEDURES, PLANS AND DETAILS
 SHALL BE SUBMITTED TO THE ENFORCEMENT AGENCY FOR
 RECORDKEEPING. EACH SHORING AND RESHORING INSTALLATION
 SHALL BE SUPERVISED, INSPECTED AND CERTIFIED TO BE IN
 COMPLIANCE WITH THE SHORING DOCUMENTS BY THE
 CONTRACTOR.
  
 2) BUILDING PROVISO: NOTICE ONLY!!! PLEASE CALL THE
 CITY OF WEST PALM BEACHS AUTOMATED TELEPHONE
 INSPECTIONS LINE (561) 805-6700) FOR ALL BUILDING
 INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS WITHOUT
 THIS THE PERMIT EXPIRES IN 6 MONTHS, ABANDONMENT OF
 JOB, NO INSPECTION ACTIVITY.
  
 3) BUILDING PROVISO: NOTICE ONLY!!! 109.3.6 THRESHOLD
 BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD
 INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED
 ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED
 FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS.
  
 4) BUILDING PROVISO!!! PLEASE NOTE ZONING REQUIREMENT:
 ART IN PUBLIC PLACES.
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 5-7) COMPLIED.
  
 8) 3RD REQUEST. PLEASE PROVIDE AN ITEMIZED LIST OF COST
 AND OVERHEAD INCLUDING THE DESIGN TEAM FEES FOR THESE
 PERMITS AND VALUE SO IT CAN BE DEDUCTED FROM THE
 CALCULATED VALUE OF THE PERMIT. THE STATED VALUE FOR
 THE BUILDING PERMIT($5,000,000.00) AND THE FOUNDATION
 PERMIT ($750,000.00) & VIBRO-PLACEMENT PERMIT
 $85,000.00 TOTALS TO $5,835,000.00 DOLLARS. THE
 CALCULATED VALUE OF THE BUILDING USING THE ICC TABLES
 IS $9,418316.00 IN CALCULATED VALUE FOR THE BUILDING.
 PLEASE PROVIDE THE VALUE OF THE FIRE SPRINKLER, FIRE
 ALARM AND ANY OTHER LOW VOLTAGE PERMIT FOR THE
 BUILDING. PLEASE PROVIDE AN ITEMIZED LIST OF THESE
 PERMITS AND VALUE SO IT CAN BE DEDUCTED FROM THE
 CALCULATED VALUE OF THE PERMIT.
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, EXHAUST
 HOODS, ANSUL SYSTEMS OR ALTERNATIVE AUTOMATIC
 FIRE-EXTINGUISHING SYSTEMS , WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE , IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 9) SEMI-COMPLIED. 3RD REQUEST. THIS REVIEW THERE WERE
 ONLY 2 SETS OF FP01 & FP11 DRAWINGS. A3RD SET OF FIRE
 PROTECTION PLANS ARE STILL REQUIRED, FOR A THRESHOLD
 BUILDING.
  
 THIS IS A 3 STORY STRUCTURE EACH FLOOR IS OVER 12,000
 SQUARE FEET IN AREA. BOTH OF THESE REQUIREMENTS WILL
 REQUIRE THE BUILDING TO BE FIRE SPRINKLERED AND HAVE
 PLANS SUBMITTED BEFORE THE ISSUANCE OF THE BUILDING
 PERMIT.
 2014 FBC-B 903.2.9 GROUP S-1. AN AUTOMATIC SPRINKLER
 SYSTEM SHALL BE PROVIDED THROUGHOUT ALL BUILDINGS
 CONTAINING A GROUP S-1 OCCUPANCY WHERE ONE OF THE
 FOLLOWING CONDITIONS EXISTS:
 1. A GROUP S-1 FIRE AREA EXCEEDS 12,000 SQUARE FEET
 (1115 M2).
 2. A GROUP S-1 FIRE AREA IS LOCATED MORE THAN THREE
 STORIES ABOVE GRADE PLANE.
  
 10-12)COMPLIED.
  
  
 13) 4/17/17 COMPLIED. EFIS REPORTS SUBMITTED FOR USE
 OVER 40 FEET, IN COMPLIANCE WITH 2014 FBC-B
 2603.5.7(1-7). J.W.
  
 14) BUILDING PROVISO/ DEFERRED SUBMITAL:
 SHEET A4.1 AND A5.3 SHOW A PREFIN METAL SHUTTER WHICH
 APPEARS WILL STAY IN THE OPEN POSITION DURING A HIGH
 WIND EVENT, PLEASE PROVIDE EITHER PRODUCT APPROVALS FOR
 SUCH OR SITE SPECIFIC ENGINEERING FOR METAL SHUTTER.
 FBC-B 3105.5.1 LOADS. RIGID AWNINGS AND CANOPY SHUTTERS
 SHALL BE DESIGNED TO RESIST THE LOADS SET FORTH IN
 CHAPTER 16 OF THIS CODE.
  
 15) BUILDING PROVISO/ DEFERRED SUBMITAL:
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 16) BUILDING PROVISO/ DEFERRED SUBMITAL:
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  