| 2017-05-31 09:00:38 | |
| | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17011176 (BUILDING PERMIT) |
| | ADD: 1620 N. CONGRESS AVE. |
| | CONT: BRICKELL GROUP |
| | TEL: 305-370-3988 |
| | TEL: 561-373-3902 / KARI |
| | E-MAIL: [email protected] |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 3RD REVIEW |
| | DATE: TUES. MAY 30, 2017 |
| | ACTION: DENIED |
| | |
| | 1) BUILDING PROVISO: NOTICE ONLY, 111 110.3.7.4.3 ALL |
| | SHORING AND RESHORING PROCEDURES, PLANS AND DETAILS |
| | SHALL BE SUBMITTED TO THE ENFORCEMENT AGENCY FOR |
| | RECORDKEEPING. EACH SHORING AND RESHORING INSTALLATION |
| | SHALL BE SUPERVISED, INSPECTED AND CERTIFIED TO BE IN |
| | COMPLIANCE WITH THE SHORING DOCUMENTS BY THE |
| | CONTRACTOR. |
| | |
| | 2) BUILDING PROVISO: NOTICE ONLY!!! PLEASE CALL THE |
| | CITY OF WEST PALM BEACHS AUTOMATED TELEPHONE |
| | INSPECTIONS LINE (561) 805-6700) FOR ALL BUILDING |
| | INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS WITHOUT |
| | THIS THE PERMIT EXPIRES IN 6 MONTHS, ABANDONMENT OF |
| | JOB, NO INSPECTION ACTIVITY. |
| | |
| | 3) BUILDING PROVISO: NOTICE ONLY!!! 109.3.6 THRESHOLD |
| | BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD |
| | INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED |
| | ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED |
| | FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS. |
| | |
| | 4) BUILDING PROVISO!!! PLEASE NOTE ZONING REQUIREMENT: |
| | ART IN PUBLIC PLACES. |
| | THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES |
| | ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR |
| | NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT |
| | APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL |
| | PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN |
| | $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE. |
| | PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND |
| | CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, |
| | ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION |
| | 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL |
| | PROJECT CONSTRUCTION COST. |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. |
| | FOR CONTACT INFORMATION PLEASE CONTACT: |
| | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR |
| | 822-1515 E-MAIL: [email protected] |
| | |
| | 5-7) COMPLIED. |
| | |
| | 8) 3RD REQUEST. PLEASE PROVIDE AN ITEMIZED LIST OF COST |
| | AND OVERHEAD INCLUDING THE DESIGN TEAM FEES FOR THESE |
| | PERMITS AND VALUE SO IT CAN BE DEDUCTED FROM THE |
| | CALCULATED VALUE OF THE PERMIT. THE STATED VALUE FOR |
| | THE BUILDING PERMIT($5,000,000.00) AND THE FOUNDATION |
| | PERMIT ($750,000.00) & VIBRO-PLACEMENT PERMIT |
| | $85,000.00 TOTALS TO $5,835,000.00 DOLLARS. THE |
| | CALCULATED VALUE OF THE BUILDING USING THE ICC TABLES |
| | IS $9,418316.00 IN CALCULATED VALUE FOR THE BUILDING. |
| | PLEASE PROVIDE THE VALUE OF THE FIRE SPRINKLER, FIRE |
| | ALARM AND ANY OTHER LOW VOLTAGE PERMIT FOR THE |
| | BUILDING. PLEASE PROVIDE AN ITEMIZED LIST OF THESE |
| | PERMITS AND VALUE SO IT CAN BE DEDUCTED FROM THE |
| | CALCULATED VALUE OF THE PERMIT. |
| | W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT |
| | FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, |
| | MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS |
| | REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID |
| | AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE |
| | ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE |
| | MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. |
| | WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING |
| | PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE |
| | QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| | SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| | QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| | LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| | FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| | LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| | EACH PERMIT. |
| | |
| | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, EXHAUST |
| | HOODS, ANSUL SYSTEMS OR ALTERNATIVE AUTOMATIC |
| | FIRE-EXTINGUISHING SYSTEMS , WALK IN COOLERS & |
| | FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| | TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| | SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, |
| | LANDSCAPE , IRRIGATION, AUGER CAST PILE AND OR |
| | FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE |
| | REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| | PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE |
| | ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE |
| | STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE |
| | REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE |
| | BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE |
| | BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR |
| | THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE |
| | PRIME OR MASTER PERMIT. |
| | |
| | 9) SEMI-COMPLIED. 3RD REQUEST. THIS REVIEW THERE WERE |
| | ONLY 2 SETS OF FP01 & FP11 DRAWINGS. A3RD SET OF FIRE |
| | PROTECTION PLANS ARE STILL REQUIRED, FOR A THRESHOLD |
| | BUILDING. |
| | |
| | THIS IS A 3 STORY STRUCTURE EACH FLOOR IS OVER 12,000 |
| | SQUARE FEET IN AREA. BOTH OF THESE REQUIREMENTS WILL |
| | REQUIRE THE BUILDING TO BE FIRE SPRINKLERED AND HAVE |
| | PLANS SUBMITTED BEFORE THE ISSUANCE OF THE BUILDING |
| | PERMIT. |
| | 2014 FBC-B 903.2.9 GROUP S-1. AN AUTOMATIC SPRINKLER |
| | SYSTEM SHALL BE PROVIDED THROUGHOUT ALL BUILDINGS |
| | CONTAINING A GROUP S-1 OCCUPANCY WHERE ONE OF THE |
| | FOLLOWING CONDITIONS EXISTS: |
| | 1. A GROUP S-1 FIRE AREA EXCEEDS 12,000 SQUARE FEET |
| | (1115 M2). |
| | 2. A GROUP S-1 FIRE AREA IS LOCATED MORE THAN THREE |
| | STORIES ABOVE GRADE PLANE. |
| | |
| | 10-12)COMPLIED. |
| | |
| | |
| | 13) 4/17/17 COMPLIED. EFIS REPORTS SUBMITTED FOR USE |
| | OVER 40 FEET, IN COMPLIANCE WITH 2014 FBC-B |
| | 2603.5.7(1-7). J.W. |
| | |
| | 14) BUILDING PROVISO/ DEFERRED SUBMITAL: |
| | SHEET A4.1 AND A5.3 SHOW A PREFIN METAL SHUTTER WHICH |
| | APPEARS WILL STAY IN THE OPEN POSITION DURING A HIGH |
| | WIND EVENT, PLEASE PROVIDE EITHER PRODUCT APPROVALS FOR |
| | SUCH OR SITE SPECIFIC ENGINEERING FOR METAL SHUTTER. |
| | FBC-B 3105.5.1 LOADS. RIGID AWNINGS AND CANOPY SHUTTERS |
| | SHALL BE DESIGNED TO RESIST THE LOADS SET FORTH IN |
| | CHAPTER 16 OF THIS CODE. |
| | |
| | 15) BUILDING PROVISO/ DEFERRED SUBMITAL: |
| | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 16) BUILDING PROVISO/ DEFERRED SUBMITAL: |
| | FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| | ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR |
| | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL |
| | 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |