| Date |
Text |
| 2017-04-06 08:51:53 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17011176 (BUILDING PERMIT) |
| | ADD: 1620 N. CONGRESS AVE. |
| | CONT: BRICKELL GROUP |
| | TEL: 305-370-3988 |
| | TEL: 561-373-3902 / KARI |
| | E-MAIL: [email protected] |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2ND REVIEW |
| | DATE: WED. APRIL 05/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. SUBMITTED SITE PLAN. |
| | |
| | 2) 2ND REQUEST. THE 2 SOILS REPORTS SUBMITTED ARE |
| | COPIES THE SIGNATURE AND SEALS ARE NOT ORIGINAL. |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| | |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS. EFFECTIVE DATE |
| | 05/06/2009. (2)(A) EVERY SHEET OF PLANS AND PRINTS |
| | WHICH MUST BE SEALED UNDER THE PROVISIONS OF CHAPTER |
| | 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY THE |
| | PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE |
| | |
| | 1ST REVIEW COMMENT. NO SOILS REPORT WAS SUBMITTED. 2014 |
| | FBC-B1803.5.2 QUESTIONABLE SOIL. WHERE THE |
| | CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL |
| | IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO |
| | THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| | OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| | GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| | |
| | 3) 2ND REQUEST / SEMI-COMPLIED. SHEET S1.0 INDICATES |
| | THE 1ST FLOOR FINISH FLOOR SLAB EL. +0 FEET 0 INCHES. |
| | PLEASE PROVIDE THE FINISH FLOOR ELEVATION IN NGVD. CITY |
| | FIRM MAPS ARE STILL IN NGVD. |
| | |
| | 4) PLEASE NOTE THIS BUILDING QUALIFIES AS A THRESHOLD |
| | BUILDING, ROOF HEIGHT OF 53 FEET THE COVER SHEET A01 |
| | BUILDING CODE SUMMARY. THRESHOLD BUILDING / FL S. S. |
| | 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING |
| | WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, |
| | OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS |
| | DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 |
| | SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN |
| | 500 PERSONS. |
| | |
| | 4A) COMPLIED. 109.3.6.1 THRESHOLD INSPECTION PLAN. |
| | |
| | 4B) 2ND REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT |
| | 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT |
| | REQUESTS FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS |
| | REQUIRED BY FL S 553.79(5) FLORIDA STATUTES TO THE |
| | MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE |
| | THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT |
| | BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO |
| | THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT |
| | ISSUANCE WILL TAKE PLACE. |
| | FORMS SENT TO E-MAIL ADDRESS: [email protected] |
| | SENT: 02/13/2017 04:09 PM. |
| | |
| | 4C) 2ND REQUEST. THRESHOLD BLDG., REQUIRED STATEMENT: |
| | W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING |
| | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 4D) COMPLIED, ONLY FOR THE SPECIAL INSPECTOR NO |
| | DESIGNEE PAPERWORK PROVIDED. |
| | 1ST ROUND OF COMMENTS. FOR THE SPECIAL INSPECTOR PLEASE |
| | PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS |
| | PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL |
| | CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL |
| | OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE |
| | RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED. |
| | UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED |
| | FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. |
| | |
| | 4E)2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB |
| | SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | 4F) 2ND REQUEST. NOTE FOR PAPER PLANS 3 SETS OF |
| | DOCUMENTS ARE REQUIRED (SOILS REPORTS, PLANS, PRODUCT |
| | APPROVALS, STRUCTURAL SHOP DRAWINGS, ETC? FOR DIGITAL |
| | PLANS, AFTER PERMIT ISSUANCE, PLEASE E-MAIL THE PERMIT |
| | LIBRARIAN OF THE PERMIT BEING ISSUED, THE PERMIT |
| | LIBRARIAN WILL THEN E-MAIL YOU THE APPROVED AND BATCH |
| | STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO SETS OF |
| | PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR THE |
| | THRESHOLD INSPECTOR, THE OTHER FOR THE MEP INSPECTORS |
| | OTHER PLANS YOU WISH TO PRINT MAYBE IN BLACK & WHITE.. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD |
| | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS |
| | CONCERNING SPECIAL INSPECTORS. |
| | |
| | 4G) NOTICE ONLY111 110.3.7.4.3 ALL SHORING AND |
| | RESHORING PROCEDURES, PLANS AND DETAILS SHALL BE |
| | SUBMITTED TO THE ENFORCEMENT AGENCY FOR RECORDKEEPING. |
| | EACH SHORING AND RESHORING INSTALLATION SHALL BE |
| | SUPERVISED, INSPECTED AND CERTIFIED TO BE IN COMPLIANCE |
| | WITH THE SHORING DOCUMENTS BY THE CONTRACTOR. |
| | |
| | 4H) NOTICE ONLY!!! PLEASE CALL THE CITY OF WEST PALM |
| | BEACHS AUTOMATED TELEPHONE INSPECTIONS LINE (561) |
| | 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF |
| | JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN |
| | 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | |
| | 4I) NOTICE ONLY!!! 109.3.6 THRESHOLD BUILDINGS, |
| | OPERATING GUIDELINES FOR THRESHOLD INSPECTORS #26. |
| | ASSURE THAT THE DESIGNER HAS REQUIRED ON THE PLANS OR |
| | SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING |
| | PENETRATIONS, FOR WALLS AND CEILINGS. |
| | |
| | 5) BUILDING PROVISO!!! PLEASE NOTE ZONING REQUIREMENT: |
| | ART IN PUBLIC PLACES. |
| | THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES |
| | ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR |
| | NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT |
| | APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL |
| | PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN |
| | $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE. |
| | PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND |
| | CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, |
| | ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION |
| | 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL |
| | PROJECT CONSTRUCTION COST. |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. |
| | FOR CONTACT INFORMATION PLEASE CONTACT: |
| | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR |
| | 822-1515 E-MAIL: [email protected] |
| | |
| | 6) 2ND REQUEST. IMPACT FEES. BEFORE A PERMIT TO |
| | CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST |
| | BE STAMPED BY THAT OFFICE, AND A COPY OF THE PAID |
| | RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL |
| | (561)233-5025 FOR MORE INFORMATION. |
| | |
| | 7)NOTICE ONLY: FOUNDATION PERMIT. 107.3.3 PHASED |
| | APPROVAL. |
| | THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION OR OTHER |
| | PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED AT THE |
| | HOLDERS OWN RISK WITH THE BUILDING OPERATION AND |
| | WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE |
| | STRUCTURE WILL BE GRANTED. NOTICE THE 1ST 7 COMMENTS |
| | ARE ALSO ON THE FOUNDATION PERMIT. |
| | |
| | VIBRO-REPLACEMENT PERMIT: 17020319, COMMENTS NEED TO BE |
| | ADDRESSED. |
| | |
| | 8) 2ND REQUEST. THE STATED VALUE FOR THE BUILDING |
| | PERMIT($5,000,000.00) AND THE FOUNDATION PERMIT |
| | ($750,000.00) TOTALS TO $5,750,000.00 DOLLARS. THE |
| | CALCULATED VALUE OF THE BUILDING USING THE ICC TABLES |
| | IS $9,418316.00 IN CALCULATED VALUE FOR THE BUILDING. |
| | PLEASE PROVIDE THE VALUE OF THE FIRE SPRINKLER, FIRE |
| | ALARM AND ANY OTHER LOW VOLTAGE PERMIT FOR THE |
| | BUILDING. PLEASE PROVIDE AN ITEMIZED LIST OF THESE |
| | PERMITS AND VALUE SO IT CAN BE DEDUCTED FROM THE |
| | CALCULATED VALUE OF THE PERMIT. |
| | |
| | W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT |
| | FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, |
| | MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS |
| | REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID |
| | AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE |
| | ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE |
| | MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. |
| | WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING |
| | PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE |
| | QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| | SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| | QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| | LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| | FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| | LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| | EACH PERMIT. |
| | |
| | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, EXHAUST |
| | HOODS, ANSUL SYSTEMS OR ALTERNATIVE AUTOMATIC |
| | FIRE-EXTINGUISHING SYSTEMS , WALK IN COOLERS & |
| | FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| | TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| | SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, |
| | LANDSCAPE , IRRIGATION, AUGER CAST PILE AND OR |
| | FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE |
| | REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| | PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE |
| | ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE |
| | STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE |
| | REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE |
| | BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE |
| | BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR |
| | THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE |
| | PRIME OR MASTER PERMIT. |
| | |
| | 9) 2ND REQUEST. NO RESPONSE COMMENT. THIS IS A 3 STORY |
| | STRUCTURE EACH FLOOR IS OVER 12,000 SQUARE FEET IN |
| | AREA. BOTH OF THESE REQUIREMENTS WILL REQUIRE THE |
| | BUILDING TO BE FIRE SPRINKLERED AND HAVE PLANS |
| | SUBMITTED BEFORE THE ISSUANCE OF THE BUILDING PERMIT. |
| | 2014 FBC-B 903.2.9 GROUP S-1. AN AUTOMATIC SPRINKLER |
| | SYSTEM SHALL BE PROVIDED THROUGHOUT ALL BUILDINGS |
| | CONTAINING A GROUP S-1 OCCUPANCY WHERE ONE OF THE |
| | FOLLOWING CONDITIONS EXISTS: |
| | 1. A GROUP S-1 FIRE AREA EXCEEDS 12,000 SQUARE FEET |
| | (1115 M2). |
| | 2. A GROUP S-1 FIRE AREA IS LOCATED MORE THAN THREE |
| | STORIES ABOVE GRADE PLANE. |
| | |
| | 10)2ND REVIEW. THIS REVIEW THERE ARE STRUCTURAL PLANS. |
| | SET # 1 SHEETS S1.0, S1.1, S2.0 & S3.0 ARE NOT SIGNED |
| | AND SEALED. PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| | DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING |
| | FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE |
| | DOCUMENT. FL ADMIN CODE 61G15-23.002 ENGINEERS. |
| | EFFECTIVE DATE 05/06/2009. (2)(A) EVERY SHEET OF PLANS |
| | AND PRINTS WHICH MUST BE SEALED UNDER THE PROVISIONS OF |
| | CHAPTER 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY |
| | THE PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. |
| | |
| | SET # 2 NONE OF THE STRUCTURAL SHEETS ARE SIGNED AND |
| | SEALED. FL ADMIN CODE 61G15-23.002 ENGINEERS. |
| | |
| | SET # 3 JUST RETURNED FROM THE PALM BEACH COUNTY IMPACT |
| | FEE OFFICE DOES NOT HAVE STRUCTURAL SHEETS. |
| | |
| | |
| | 11) 2ND REQUEST. SEMI-COMPLIED. LIFE SAFETY PLAN. THE |
| | LIFE SAFETY PLAN A0.5 AND A6.1 BOTH SHOW THE 2 |
| | STAIRWELLS WITH A CLEAR WIDTH OF 4 FOOT- 1 INCH. THE |
| | COVERSHEET UNDER EGRESS CAPACITY LIST THE STAIR AS 3 |
| | FOOT WIDE. THE CODE EXCEPTION TAKEN IS 1009.4.EXCEPTION |
| | # 1. PLEASE NOTE THE EXCEPTION # 1 IS THE TOTAL |
| | OCCUPANT LOAD IS TO BE TAKEN FOR THE FLOOR. THE 2012 |
| | IBC- AND COMMENTARY IS THE BASE CODE THE 2014 FBC-B IS |
| | DERIVED FROM. SEE 1005.3.1 PAGE 10-16 SECTION 1009.1. |
| | EXCEPTION 1, IS APPLICABLE ONLY WHEN THE ENTIRE |
| | OCCUPANT LOAD OF A STORY IS LESS THAN 50. |
| | |
| | |
| | |
| | 12) 2ND REQUEST. THE RESPONSE NARRATIVE REFERS BACK TO |
| | SPECIFICATIONS SECTION 8.03 ON SHEET A-04. |
| | EITHER THE SPECIFICATION SECTION 8.03 IS NOT CODE |
| | COMPLIANT OR NOT COVERED IN THIS SECTION, SEE THE CODE |
| | REQUIREMENTS THAT WERE REFERENCED UNDER THE 1ST REVIEW: |
| | 2014 FBC-B 1008.1.4.3 HORIZONTAL SLIDING DOORS.IN OTHER |
| | THAN GROUP H OCCUPANCIES, HORIZONTAL SLIDING DOORS |
| | PERMITTED TO BE A COMPONENT OF A MEANS OF EGRESS IN |
| | ACCORDANCE WITH EXCEPTION 6 TO SECTION 1008.1.2 SHALL |
| | COMPLY WITH ALL OF THE FOLLOWING CRITERIA: |
| | |
| | COMPLIED. 1. THE DOORS SHALL BE POWER OPERATED AND |
| | SHALL BE CAPABLE OF BEING OPERATED MANUALLY IN THE |
| | EVENT OF POWER FAILURE. |
| | |
| | COMPLIED. 2. THE DOORS SHALL BE OPENABLE BY A SIMPLE |
| | METHOD FROM BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR |
| | EFFORT. |
| | |
| | 3) 2ND REQUEST. PLEASE UPDATE PLANS, THE PLANS INDICATE |
| | 50 LBS. TO SET THE DOOR IN MOTION AND THERE IS NO |
| | REFERENCE TO THE 15 LBS. TO CLOSE THE DOOR. |
| | CODE SECTION (3). THE FORCE REQUIRED TO OPERATE THE |
| | DOOR SHALL NOT EXCEED 30 POUNDS (133 N) TO SET THE DOOR |
| | IN MOTION AND 15 POUNDS (67 N) TO CLOSE THE DOOR OR |
| | OPEN IT TO THE MINIMUM REQUIRED WIDTH. |
| | |
| | 4) .2ND REQUEST.(4) THE DOOR SHALL BE OPENABLE WITH A |
| | FORCE NOT TO EXCEED 15 POUNDS (67 N) WHEN A FORCE OF |
| | 250 POUNDS (1100 N) IS APPLIED PERPENDICULAR TO THE |
| | DOOR ADJACENT TO THE OPERATING DEVICE. |
| | |
| | 5. NOT REQUIRED. THE DOOR ASSEMBLY SHALL COMPLY WITH |
| | THE APPLICABLE FIRE PROTECTION RATING AND, WHERE RATED, |
| | SHALL BE SELF-CLOSING OR AUTOMATIC CLOSING BY SMOKE |
| | DETECTION IN ACCORDANCE WITH SECTION 716.5.9.3, SHALL |
| | BE INSTALLED IN ACCORDANCE WITH NFPA 80 AND SHALL |
| | COMPLY WITH SECTION 716. |
| | |
| | 6. 2ND REQUEST.(6)THE DOOR ASSEMBLY SHALL HAVE AN |
| | INTEGRATED STANDBY POWER SUPPLY. |
| | |
| | 7. 2ND REQUEST.(7) THE DOOR ASSEMBLY POWER SUPPLY SHALL |
| | BE ELECTRICALLY SUPERVISED. |
| | |
| | 8.2ND REQUEST.(8) THE DOOR SHALL OPEN TO THE MINIMUM |
| | REQUIRED WIDTH WITHIN 10 SECONDS AFTER ACTIVATION OF |
| | THE OPERATING DEVICE. |
| | |
| | 1ST REVIEW COMMENT: SHEETS A1.1 & A1.2 BOTH HAVE A DOOR |
| | DESIGNATED A W5 OR A HORIZONTAL SLIDING DOOR. PLEASE |
| | SHOW COMPLIANCE WITH 2014 FBC-B 1008.1.4.3 (1-8). THERE |
| | ARE ISSUES THAT SECTION 8.03 EITHER ARE NOT CODE |
| | COMPLIANT OR NOT COVERED IN THIS SECTION. SEE LIST |
| | BELOW: |
| | |
| | 13) 4/17/17 COMPLIED. EFIS REPORTS SUBMITTED FOR USE |
| | OVER 40 FEET, INCOMPLIANE WITH 2014 FBC-B |
| | 2603.5.7(1-7). J.W. |
| | |
| | 14) BUILDING PROVISO/ DEFERRED SUBMITAL: |
| | SHEET A4.1 AND A5.3 SHOW A PREFIN METAL SHUTTER WHICH |
| | APPEARS WILL STAY IN THE OPEN POSITION DURING A HIGH |
| | WIND EVENT, PLEASE PROVIDE EITHER PRODUCT APPROVALS FOR |
| | SUCH OR SITE SPECIFIC ENGINEERING FOR METAL SHUTTER. |
| | FBC-B 3105.5.1 LOADS. RIGID AWNINGS AND CANOPY SHUTTERS |
| | SHALL BE DESIGNED TO RESIST THE LOADS SET FORTH IN |
| | CHAPTER 16 OF THIS CODE. |
| | |
| | 15) BUILDING PROVISO/ DEFERRED SUBMITAL: |
| | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 16) BUILDING PROVISO/ DEFERRED SUBMITAL: |
| | FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| | ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR |
| | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL |
| | 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |