Plan Review Notes
Plan Review Notes For Permit 17011176
Permit Number 17011176
Review Stop P
Sequence Number 1
Notes
Date Text
2017-03-02 12:15:231ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. WILL THE SINGLE USER BATHROOM NEXT TO THE RETAIL
 SPACE BE ACCESSIBLE FOR THE OCCUPANTS OF THE RETAIL
 SPACE TO USE, IT APPEARS THAT IT CAN ONLY BE ACCESSED
 THROUGH THE STORAGE FACILITY PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 2. THE COFFEE BAR SHALL COMPLY WITH FBC ACC
 902.2,902.3, 308
  
 3.SHT.P0.2 WATER HEATER DETAIL SHALL SHOW PAN. PER FBC
 PL 504.7
  
 4.P1.1. P1.2 DISCHARGE FROM ELEVATOR SUMP SHALL
 TERMINATE A MIN OF 12" FROM BUILDING. FBC 1503.7
  
 5. A CLEAN OUT IS REQUIRED AT THE BASE OF ANY WASTE OR
 SOIL STACK. PER FBC PL 708.3.4
  
 6. A CLEAN OUT IS REQUIRED @ 100' INTERVALS IN THE
 BUILDING SEWER. PER FBC PL 708.3.2
  
 7. TEMPERED WATER IS REQUIRE AT ALL LAVATORY'S IN
 PUBLIC BATHROOMS. PER FBC PL 416.5
  
 8.SHOW THE REQUIRED TRAP PRIMERS ON ALL FLOOR DRAINS.
 PER FBC PL 1002.4
  
 9. PLEASE PROVIDE A WATER RISER. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
  
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  