Plan Review Notes
Plan Review Notes For Permit 17011176
Permit Number 17011176
Review Stop M
Sequence Number 1
Notes
Date Text
2017-02-02 16:59:571ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17011176
 2/2/17
  
 1) THE PROPOSED BUILDING SHALL BE IN DESIGNED AND
 CONSTRUCTED IN ACCORDANCE WITH THE FBC-14 ENERGY
 CONSERVATION CODE. REFER TO SECTIONS C101.2 AND C401.2
 AND PROVIDE COMPLIANCE DOCUMENTATION.
  
 2) PROVIDE AC COOLING AND HEATING CALCULATIONS IN
 COMPLIANCE WITH SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
  
 3) SHEET M0.1, NOTE #15: PLEASE UPDATE THE SMACNA
 REFERENCE TO THE CURRENT 2005 EDITION AND PROVIDE
 TYPICAL DUCT HANGING AND CONNECTION DETAILS ON THE
 PLANS.
  
 4) M0.1, NOTE #34: PLEASE CLARIFY IF THE AC SYSTEMS
 WILL BE LINKED TOGETHER FOR SIMULTANEOUS FAN SHUTDOWN
 IF ANY SINGLE DUCT SMOKE DETECTOR ACTIVATES.
  
 5) M0.2: PROVIDE THE WIND DESIGN CRITERIA FOR
 INSTALLATION OF THE CONDENSERS IN COMPLIANCE WITH
 SECTION 301.15 FBC-14 MECHANICAL, AND SECTION 1609
 FBC-14 BUILDING.
  
 6) SUBMIT TWO COPIES OF A VALID FLORIDA PRODUCT
 APPROVAL AND/OR MIAMI-DADE NOA FOR THE O/A INTAKE AND
 EXHAUST LOUVERS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  