| 2017-02-02 16:59:57 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17011176 | | | 2/2/17 | | | | | | 1) THE PROPOSED BUILDING SHALL BE IN DESIGNED AND | | | CONSTRUCTED IN ACCORDANCE WITH THE FBC-14 ENERGY | | | CONSERVATION CODE. REFER TO SECTIONS C101.2 AND C401.2 | | | AND PROVIDE COMPLIANCE DOCUMENTATION. | | | | | | 2) PROVIDE AC COOLING AND HEATING CALCULATIONS IN | | | COMPLIANCE WITH SECTION C403.2.1 FBC-14 ENERGY | | | CONSERVATION. | | | | | | 3) SHEET M0.1, NOTE #15: PLEASE UPDATE THE SMACNA | | | REFERENCE TO THE CURRENT 2005 EDITION AND PROVIDE | | | TYPICAL DUCT HANGING AND CONNECTION DETAILS ON THE | | | PLANS. | | | | | | 4) M0.1, NOTE #34: PLEASE CLARIFY IF THE AC SYSTEMS | | | WILL BE LINKED TOGETHER FOR SIMULTANEOUS FAN SHUTDOWN | | | IF ANY SINGLE DUCT SMOKE DETECTOR ACTIVATES. | | | | | | 5) M0.2: PROVIDE THE WIND DESIGN CRITERIA FOR | | | INSTALLATION OF THE CONDENSERS IN COMPLIANCE WITH | | | SECTION 301.15 FBC-14 MECHANICAL, AND SECTION 1609 | | | FBC-14 BUILDING. | | | | | | 6) SUBMIT TWO COPIES OF A VALID FLORIDA PRODUCT | | | APPROVAL AND/OR MIAMI-DADE NOA FOR THE O/A INTAKE AND | | | EXHAUST LOUVERS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|