| Plan Review Notes For Permit 17011163 |
| Permit Number |
17011163 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-02-01 06:05:42 | 1) THERE ARE NO PIPE SIZES ON THE PLUMBING DRAWING. A | | | PLAN REVIEW CANNOT BE PERFORMED WITHOUT ALL SECTIONS OF | | | THE DRAIN, WASTE AND VENT SECTIONS PROPERLY SIZED IN | | | ACCORDANCE WITH FBC-RESIDENTIAL SEC.P3108.3, P3005.4.1. | | | 2) INDICATE ON THE PLUMBING DRAWING WHAT PIPING IS NEW | | | AND WHAT IS EXISTING TO REMAIN OR REPLACED. WPB AMEND. | | | TO FBC SEC. 107.2.1. | | | 3) A KITCHEN SINK IS NOT PERMITTED ON A WET VENT. | | | FBC-RES. SEC.P3108.1. | | | 4) HOW IS WATER BEING SUPPLIED TO THE NEW WASHING | | | MACHINE? SUBMIT A WATER RISER FOR REVIEW WITH PIPE | | | SIZES. WPB AMEND. TO FBC SEC.107.2.1, 107.3.5.3. | | | 5) SUBMIT TWO COPIES OF A FLOOR PLAN SHOWING THE | | | LOCATION OF THE NEW WASHING MACINE AND CLEARLY SHOWING | | | ALL AREAS OF WHERE WORK IS BEING DONE.WPB AMEND. TO FBC | | | SEC. 107.2.1. | | | 6) THE APPLICATION NOTES A BEDROOM AND KITCHEN | | | RENOVATION IS BEING DONE.SUBMIT COMPLETE PLANS FOR THE | | | RENOVATION INCLUDING BUILDING, ELECTRICAL, ETC. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|