| Plan Review Notes For Permit 17011146 |
| Permit Number |
17011146 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-02-06 13:54:52 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17011146 | | | 2/6/17 | | | | | | 1) PLEASE PROVIDE A SCOPE OF WORK FOR MECHANICAL WITH | | | CORRESPONDING DRAWINGS, DETAILS, AND SPECIFICATIONS. | | | PLEASE INCLUDE: | | | | | | A) MINIMUM VENTILATION CALCULATIONS- TABLE 403.3 | | | | | | B) AC COOLING AND HEATING CALCULATIONS- C403.2.1 FBC-14 | | | ENERGY CONSERVATION CODE | | | | | | C) ENERGY COMPLIANCE SUBMITTAL DOCUMENTS- C101.4.3 | | | | | | D) DUCTWORK LAYOUT PLANS AND DETAILS- SECTION 601.1 | | | | | | E) MECHANICAL EQUIPMENT SCHEDULES. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|