| Plan Review Notes For Permit 17011146 |
| Permit Number |
17011146 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-02-06 14:58:39 | ELECTRICAL REVIEW NOTES | | | REVIEWED FOR COMPLIANCE WITH: | | | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) | | | | | | PROJECT NAME: | | | JOB ADDRESS: 515 PALM STREET | | | DESCRIPTION: ADDITION ON EXISTING SPACE | | | MASTER PERMIT: 17011146 | | | | | | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. | | | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF | | | SUBMITTED CORRECTIONS. | | | | | | 1. THOUGH YOU ALLEGE NOT TO BE DOING ANY ELECTRICAL | | | WORK, ON SHEET A1 YOU MENTION THE REMOVAL OF ALL | | | ELECTRIC IN A WALL THAT IS TO BE DEMOLISHED. | | | 2. THE EXISTING LIGHTING SHALL BE COMPLIANT WITH CODE | | | REQUIREMENTS. A LIGHT DENSITY ALLOWANCE CHART AS | | | PROVIDED IN FBC-EC 405.5.2. | | | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER | | | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER | | | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD | | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID | | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE | | | GREATLY APPRECIATED. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU, | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | PH: 561-805-6746 | | | EMAIL: [email protected] | | | |
|