| Plan Review Notes For Permit 17011073 |
| Permit Number |
17011073 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-03-07 16:48:21 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1- SHEET CS1: REVISE THE EXPOSURE CATEGORY. ACCORDING | | | TO SEC. R301.2.1.4 FBC-RESIDENTIAL THIS BUILDINGS | | | LOCATED IN EXPOSURE "C" NOT "B". REVISE AS REQUIRED AND | | | REVISE THE DESIGN PRESSURES ON SHEET 5B. ALSO, CLARIFY | | | WHY THE DESIGN PRESSURES FOR WINDOW #002 IS -00.00? | | | 2- PROVIDE COMPLETE GARAGE DOOR STRUCTURAL BUCK DETAIL. | | | SPECIFY STRUCTURAL BUCK SIZE AND FASTENER TYPE AND | | | SPACING. | | | 3- REVISE ENERGY CALCULATIONS SUBMITTED: | | | A) REVISE DOOR TYPE INFORMATION SHOWN ON PAGE 3 OF 4. | | | WHERE ARE THE WOOD DOORS. PRODUCT APPROVAL FOR ENTRY | | | DOORS IS FOR GLAZED FIBERGLASS DOOR. THIS DOOR NEEDS TO | | | BE ENTERED IN THE WINDOW AREA. | | | B) REVISE THE WALL TYPE SPECIFIED ON PAGE 3 OF 4 FOR | | | THE GARAGE AREA. ACCORDING TO THE WCI/PLAN STANDARDS ON | | | SHEET 6A ALL INTERIOR WALLS ARE METAL NOT WOOD. |
|