Plan Review Notes
Plan Review Notes For Permit 17011073
Permit Number 17011073
Review Stop B
Sequence Number 1
Notes
Date Text
2017-03-06 18:06:41NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE; FBC 5TH EDITION (2014).
  
 1- SHEET CS1: REVISE THE EXPOSURE CATEGORY. ACCORDING
 TO SEC. R301.2.1.4 FBC-RESIDENTIAL THIS BUILDINGS
 LOCATED IN EXPOSURE "C" NOT "B". REVISE AS REQUIRED AND
 REVISE THE DESIGN PRESSURES ON SHEET 5B. ALSO, CLARIFY
 WHY THE DESIGN PRESSURES FOR WINDOW #002 IS -00.00?
  
 2- PROVIDE COMPLETE GARAGE DOOR STRUCTURAL BUCK DETAIL.
 SPECIFY STRUCTURAL BUCK SIZE AND FASTENER TYPE AND
 SPACING. SEC. R301.1 FBC-RESIDENTIAL.
  
 3- REVISE ENERGY CALCULATIONS SUBMITTED:
 A) REVISE/CLARIFY DOOR TYPE INFORMATION SHOWN ON PAGE 3
 OF 4. WHERE ARE THE WOOD DOORS. PRODUCT APPROVAL FOR
 ENTRY DOORS IS FOR GLAZED FIBERGLASS DOOR. THIS DOOR
 NEEDS TO BE ENTERED IN THE WINDOW AREA AS REQUIRED BY
 SEC. R405.5.3.3 FBC-ENERGY CONSERVATION.
  
 B) REVISE THE WALL TYPE SPECIFIED ON PAGE 3 OF 4 FOR
 THE GARAGE AREA. ACCORDING TO THE WCI/PLAN STANDARDS ON
 SHEET 6A ALL INTERIOR WALLS ARE METAL NOT WOOD. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 ******PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 *****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  