| 2017-03-06 18:06:41 | NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW |
| | COMMENTS. |
| | CODE; FBC 5TH EDITION (2014). |
| | |
| | 1- SHEET CS1: REVISE THE EXPOSURE CATEGORY. ACCORDING |
| | TO SEC. R301.2.1.4 FBC-RESIDENTIAL THIS BUILDINGS |
| | LOCATED IN EXPOSURE "C" NOT "B". REVISE AS REQUIRED AND |
| | REVISE THE DESIGN PRESSURES ON SHEET 5B. ALSO, CLARIFY |
| | WHY THE DESIGN PRESSURES FOR WINDOW #002 IS -00.00? |
| | |
| | 2- PROVIDE COMPLETE GARAGE DOOR STRUCTURAL BUCK DETAIL. |
| | SPECIFY STRUCTURAL BUCK SIZE AND FASTENER TYPE AND |
| | SPACING. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | 3- REVISE ENERGY CALCULATIONS SUBMITTED: |
| | A) REVISE/CLARIFY DOOR TYPE INFORMATION SHOWN ON PAGE 3 |
| | OF 4. WHERE ARE THE WOOD DOORS. PRODUCT APPROVAL FOR |
| | ENTRY DOORS IS FOR GLAZED FIBERGLASS DOOR. THIS DOOR |
| | NEEDS TO BE ENTERED IN THE WINDOW AREA AS REQUIRED BY |
| | SEC. R405.5.3.3 FBC-ENERGY CONSERVATION. |
| | |
| | B) REVISE THE WALL TYPE SPECIFIED ON PAGE 3 OF 4 FOR |
| | THE GARAGE AREA. ACCORDING TO THE WCI/PLAN STANDARDS ON |
| | SHEET 6A ALL INTERIOR WALLS ARE METAL NOT WOOD. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | ******PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | *****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| | FOR REFERENCE. |
| | |