| Plan Review Notes For Permit 17011057 |
| Permit Number |
17011057 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-02-24 11:51:04 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | PROVISO COMMENTS: | | | | | | 1. PLEASE SHOW ON DOCUMENTS THE ELECTRICAL INFORMATION | | | OF FEEDER AND BRANCH CIRCUITS FEEDING SPLASH PAD PUMPS. | | | REFER TO MASTER DRAWINGS SHOWING LOADS AND PANEL BOARDS | | | FEEDING AREA. | | | 2. FEEL FREE TO CONTACT ME AT THE NUMBER LISTED BELOW | | | SHOULD YOU HAVE ANY QUESTIONS OR CONCERNS. | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | |
|