| 2017-02-14 11:16:56 | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 |
| | COMMENTS: |
| | |
| | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE |
| | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE |
| | PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL |
| | LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE |
| | ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, CARD |
| | READERS, GENERATOR, KITCHEN HOODS ETC. A NOTE WILL |
| | SUFFICE. |
| | 2. ADD A GENERAL NOTE TO PROVIDE PER FBC EC 405.7.4- |
| | COMPLETION DOCUMENTS PER CODE SECTION. FBC EC 405.7.3- |
| | VOLTAGE DROP |
| | 3. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO |
| | INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC |
| | 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE |
| | VERBIAGE IN CODE. |
| | 4. PROVIDE THE AVAILABLE FAULT CURRENT AT THE UTILITY |
| | TRANSFORMER. FBC 107.3.5 |
| | 5. PER FBC EC 405.7- A MINIMUM OF 50% OF ALL 125V, 15 |
| | AND 20AMP RECEPTACLES SHALL BE AUTOMATICALLY CONTROLLED |
| | WHERE INSTALLED IN PRIVATE OR OPEN OFFICES AND COMPUTER |
| | CLASSROOMS. THIS INCLUDES MODULAR PARTITIONS TOO. SHOW |
| | COMPLIANCE ACCORDINGLY. |
| | 6. PROVIDE A NOTE TO INDICATE COMPLIANCE WITH FBC EC |
| | 405.2 AUTOMATIC LIGHTING CONTROL AND LIGHTING DENSITIES |
| | PER CODE SECTION. |
| | 7. PLEASE ADDRESS BUILDING, FIRE AND MECHANICAL |
| | COMMENTS RELATED TO ELECTRICAL. |
| | 8. PROVIDE A NOTE ON PLANS TO INDICATE NEC 300.5 |
| | REQUIREMENTS FOR ALL UNDERGROUND RACEWAYS. |
| | 9. PROVIDE ?? DETAIL OF ELECTRICAL ROOMS TO VERIFY |
| | CLEARANCE. FBC 107.3.5 |
| | 10. PROVIDE GFCI PROTECTION FOR ALL RECEPTACLES IN THE |
| | BASEMENT AREA AND MAINTENANCE SECTION PER NEC 210.8B |
| | (6)INDOOR WET LOCATION (8) SIMILAR AREAS WHERE |
| | ELECTRICAL DIAGNOSTIC EQUIPMENT, ELECTRICAL HAND TOOLS |
| | ARE TO BE USED.- THAT WILL INCLUDE ALL 125V SINGLE |
| | PHASE 15 OR 20A RECEPTACLES. |
| | 11. PLEASE NOTE THAT THE SEPARATE GENERATOR PERMIT |
| | REQUIRED WILL NEED TO PROVIDE A SELECTED LOAD |
| | ARRANGEMENT BASED ON CUSTOMER SELECTED LOADS. MANUAL |
| | TRANSFER SELECTED. NEC 702.4.B1. ALSO SIGNAGE IS TO BE |
| | PROVIDED PER NEC 702.7A. A NOTE WILL SUFFICE |
| | 12. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL |
| | FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS |
| | REGARDING THIS PROJECT. |
| | |
| | |