| 2017-02-14 09:09:58 | ****CORRECTIONS**** |
| | REVISED 3/10 |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 3/10 - SEE COMMENTS FOR PERMIT #16110061. SEVERAL |
| | ISSUES AFFECT THE STRUCTURE PERMIT: |
| | 1. SPECIFY VERTICAL DATUM (NAVD88 OR NGVD29). NGVD29 IS |
| | THE CITY STANDARD AND IS THE ONE SPECIFIED ON CIVIL |
| | PAGES WHICH WERE NOT PROVIDED FOR THIS REVIEW. |
| | |
| | 2. CONNECTOR FASTENERS ON S102 ARE NOT CONSISTENT WITH |
| | THE SIMPSON CATALOG, REVISE OR PROVIDE CALCULATIONS. |
| | |
| | 3. ARCHITECT'S SEAL IS NOT CONSISTENT WITH FLORIDA |
| | BOARD OF ARCHITECT'S SEAL REQUIREMENTS, REVISE OR EMAIL |
| | TO ADVISE OBJECTION PRIOR TO RESUBMITTAL. |
| | |
| | 4. A SHEETS INCLUDE A TITLE BLOCK FOR RANDALL STOFFT, |
| | BUT ARE SIGNED BY DON DURANTE. SEE FAC FOR BOARD TITLE |
| | BLOCK AND SIGNATURE REQUIREMENTS; EITHER REVISE TITLE |
| | BLOCK OR HAVE RANDALL STOFFT SIGN. |
| | |
| | 5. THIS MAY BE A THRESHOLD BUILDING; THRESHOLD |
| | STATEMENT REQUIRED ON PLANS, SPECIAL INSPECTOR, ETC. |
| | SEE 16110061. |
| | |
| | 6. SEE 16110061 REVIEW FOR COMMENTS REGARDING WIND |
| | DESIGN (OPEN BUILDING) WHICH AFFECT THIS STRUCTURE |
| | PERMIT APPLICATION. |
| | |
| | *************************************** |
| | |
| | 1. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC |
| | 109. VALUE IS TO INCLUDE LABOR, MATERIALS, OVERHEAD, |
| | PROFIT, EVEN IF PROVIDED BY OTHERS. |
| | |
| | 2. THE SITE PLAN (A004) SHOWS TRACT NUMBERS BUT DOES |
| | NOT APPEAR TO INCLUDE PROPERTY LINES. REVISE PLAN TO |
| | SHOW COMPLIANCE WITH FBC TABLES 602, 705.8. |
| | |
| | 3. S003, 4820, NOTES 4 - 6 REFERS TO A SPLICE TABLE |
| | "BELOW", UNABLE TO LOCATE, PLEASE REVISE PLAN TO |
| | PROVIDE OR REMOVE REFERENCES. NOTE THAT SOME DETAILS |
| | INCLUDE LAP SPLICE REQUIREMENTS (FOR EXAMPLE, 40 BAR |
| | DIAM. S301, 36 BAR DIAM. S304), BUT NOT ALL DETAILS |
| | INCLUDE THE SPEC. DETAIL 2-S305 REFERS TO THE TABLE. |
| | |
| | 4. S004, CLARIFY NOMINAL C&C WIND PRESSURES FOR THE |
| | OPEN BLDG (PORTE COCHERE). THIS AREA DOES NOT MEET THE |
| | DEFINITION OF "OPEN" PER FBC 1609, ASCE 7-10. |
| | |
| | 5. COURTESY NOTIFICATION - THE WEBSITE |
| | WWW.MYFLORIDALICENSE.COM DOES NOT SHOW THAT ENGINEER |
| | JAMES C. MULLEN HAS NOT COMPLETED THE FLORIDA BUILDING |
| | CODE COURSE. THIS COMMENT WILL NOT DELAY ISSUANCE OF |
| | THIS PERMIT; HOWEVER, IF ENGINEER HAS NOT COMPLETED THE |
| | COURSE AND HAD THE WEBSITE UPDATED PRIOR TO |
| | RESUBMITTAL, FBPE WILL BE ADVISED AS REQUIRED BY |
| | FLORIDA STATUTE. |
| | |
| | (ALL OTHER LICENSEES VERIFIED) |
| | |
| | 6. SEE SIGNATURE REVIEW AND RESOLVE ISSUE WITH |
| | ARCHITECT'S DIGITAL SIGNATURE. ***DO NOT DELAY |
| | RESUBMITTAL*** PLEASE CONTACT ME REGARDING ALTERNATIVE |
| | METHODS OF COMPLIANCE IF THIS CANNOT BE RESOLVED PRIOR |
| | TO RESUBMITTAL. |
| | |
| | PROVISO |
| | |
| | FBC 1008.1.10, PANIC BARS REQUIRED (OCCUPANT LOAD > 49 |
| | ASSEMBLY OCCUPANCY) |
| | |
| | ACCESSIBILITY, LIFE SAFETY NOT REVIEWED - THIS PERMIT |
| | WILL BE ISSUED AT APPLICANT'S RISK |
| | |
| | |
| | |