| 2017-05-03 18:01:02 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND MECHANICAL |
| | REVIEW CHECKLIST. |
| | CODE: FBC, 5TH EDITION (2014). |
| | |
| | |
| | NOTE: |
| | COMMENTS BELOW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS THAT CONTRACTOR AGREES TO PROVIDE THE REQUIRED |
| | INFORMATION AFTER THE PERMIT IS ISSUED BUT BEFORE |
| | INSPECTIONS TO AVOID CONFLICTS/DELAYS. NOTE: REVISION |
| | FEES APPLY. CONTRACTOR TO ADVICE IN WRITING IF PROVISO |
| | OPTION IS PREFERRED AT THIS TIME. |
| | |
| | |
| | 1- REVISE EQUIPMENT SIZING CALCULATIONS SUBMITTED; |
| | CALCULATIONS ARE DONE FOR WORST CASE SCENARIO. |
| | CALCULATIONS NEED TO BE DONE FOR THE ACTUAL ORIENTATION |
| | OF THE BUILDING AS REQUIRED BY SEC. R403.6.1 FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | RESPONSE: REPEAT COMMENT. CALCULATIONS SUBMITTED ARE |
| | DONE FOR THE WORST CASE SCENARIO AGAIN. CALCULATIONS |
| | NEED TO BE DONE FOR THE ACTUAL ORIENTATION OF THE |
| | BUILDING. NOTE: SEE BUILDING REVIEW COMMENTS FOR |
| | COMMENTS REGARDING THE ENERGY CALCULATIONS ACTUAL |
| | ORIENTATION OF THE BUILDING. |
| | |
| | 2- EQUIPMENT SHOWN ON-THE A/C PLAN SUBMITTED DOESN'T |
| | MATCH INFORMATION SHOWN ON THE ENERGY CALCULATIONS AND |
| | EQUIPMENT SIZING CALCULATIONS. REVISE AS REQUIRED TO |
| | MATCH. SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD |
| | DRAWIINGS FOR REFERENCE. |
| | |