| Plan Review Notes For Permit 17010997 |
| Permit Number |
17010997 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-07 10:27:56 | NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW | | | COMMENTS. | | | CODE: FBC, 5TH EDITION (2014). | | | | | | 1- REVISE EQUIPMENT SIZING CALCULATIONS SUBMITTED; | | | CALCULATIONS ARE DONE FOR WORST CASE SCENARIO. | | | CALCULATIONS NEED TO BE DONE FOR THE ACTUAL ORIENTATION | | | OF THE BUILDING AS REQUIRED BY SEC. R403.6.1 FBC-ENERGY | | | CONSERVATION, 5TH EDITION (2014). | | | | | | | | | | | | ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD | | | DRAWIINGS FOR REFERENCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|