2017-03-03 15:14:10NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: FBC, 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT. COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED
 LAND DEVELOPMENT CODE.
  
 2- PROVIDE SOIL TEST REPORT (2 COPIES). SEC. R401.4
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 3- PROVIDE SURFACE DRAINAGE PLAN (2 COPIES) SHOWING
 COMPLIANCE WITH SEC. R401.3 FBC-RESIDENTIAL.
  
 4- ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL THIS
 BUILDING IS LOCATED IN EXPOSURE "D" NOT "C". REVISE ALL
 THE DESIGN INFORMATION SHOWN ON SHEET D1 AND ALL THE
 DESIGN PRESSURES SHOWN ON SHEET 1 OF 7.
 NOTE: PRODUCT APPROVALS WILL BE REVIEWED ONCE DESIGN
 PRESSURES ARE REVISED. ENGINEER OF RECORD TO REVIEW AND
 APPROVE ALL PRODUCT APPROVALS AFTER THE DESIGN
 PRESSURES ARE REVISED.
  
 5- REVISE ALL ROOF LOADS SHOWN ON SHEET D1 TO INCLUDE
 THE ATTIC LIVE LOADS REQUIRED BY NOTES "B" AND "G" OF
 TABLE R301.5 FBC-RESIDENTIAL.
  
 6- SHEET D1: CLARIFY THE REQUIRED SOIL BEARING
 CAPACITY. NOTE #14 OF THE 2014 FBC RESIDENTIAL NOTES
 SPECIFY 2,000 PSF SOIL BEARING CAPACITY, WHILE NOTE # 5
 ON THE TOP RIGHT HAND SIDE OF THE SHEET AND TYPICAL
 WALL SECTION CALL FOR 2,500 PSF. REVISE AS REQUIRED TO
 MATCH. SEC. R301.1 FBC-RESIDENTIAL.
  
 7- ROOF FRAMING PLAN (TRUSS LAYOUT):
 A) REVISE THE DESIGN CRITERIA. THE BUILDING EXPOSURE IS
 "D" NOT "C". SEC. R301.2.1.4 FBC-RESIDENTIAL. REVISE
 ALL THE DESIGN PRESSURES ACCORDINGLY.
  
 B) LETTERING ON THE STRAPPING & NAILING REQUIREMENT IS
 NOT LEGIBLE. IT'S TOO SMALL. REVISE AS REQUIRED. SEC.
 107.2.1.4 CITY AMENDMENTS.
  
 8- TRUSS PACKAGE SUBMITTED.
 A) REVISE THE DESIGN CRITERIA. THE BUILDING EXPOSURE IS
 "D" NOT "C". SEC. R301.2.1.4 FBC-RESIDENTIAL. REVISE
 THE DESIGN PRESSURES ACCORDINGLY.
  
 B) TRUSS ENGINEER TO SIGN AND SEAL ALL SHEETS AS
 REQUIRED BY CHAPTER 471 F.S. AND 61G15-23.002.
  
 C) TRUSS ENGINEER TO PROVIDE TITTLE BLOCK IN ALL SHEETS
 AS REQUIRED BY CHAPTER 471 F.S. AND 61G15-23.002.
  
 D) ENGINEER OF RECORD TO REVIEW AND APPROVE ALL TRUSS
 DRAWINGS PRIOR TO-SUBMITTAL. SEC. 107.3.4.2 CITY
 AMENDMENTS.
  
 9- SPECIFY SELF CLOSING DEVICE FOR THE GARAGE SWING
 DOOR LEADING TO THE HOUSE AS REQUIRED BY SEC. R302.5.1
 FBBC-RESIDENTIAL.
  
 10- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE ENTRY AREA AND COVERED PATIO
 SOFFITS SHOWING COMPLIANCE WITH SEC. R703.1.3
 FBC-RESIDENTIAL. SPECIFY ALL MATERIALS AND FASTENING.
  
 11- PROPERTY IS LOCATED IN FLOOD ZONE "B" NOT "C".
 REVISE INFORMATION ON SURVEY. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 12- REVISE ENERGY CALCULATIONS SUBMITTED;
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING PROJECT ADDRESS AND OWNER'S NAME. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 B) PROVIDE THE NAME OF THE INDIVIDUAL COMPLETING THE
 COMPLIANCE REPORT AS REQUIRED BY SEC. R405.4.2
 FBC-ENERGY CONSERVATION.
  
 NOTE: LABELS WILL BE REQUIRED FOR THE WINDOWS AND DOORS
 SHOWING THE U-FACTOR AND SHGC FACTOR SPECIFIED ON THE
 ENERGY CALCULATIONS.
  
 13- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ROOF RIDGE VENT AS SPECIFIED ON PLANS.
  
 B) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 ENGINEER OF RECORD TO LIST THE 2014 FLORIDA PRODUCT
 APPROVAL NUMBER NEXT TO EACH SPECIFIED CONNECTOR. NOTE:
 FLORIDA PRODUCT APPROVAL NUMBERS LISTED ON THE ROOF
 FRAMING PLANS (TRUSS LAYOUT) ARE FOR THE 2010 CODE
 VERSION. NEED FLORIDA PRODUCT APPROVAL NUMBER FOR THE
 CURRENT 2014 CODE.
  
 D) ROOF SHINGLES. FLORIDA PRODUCT APPROVAL FL10124-R5
 SUBMITTED WAS REVISED. NEED TO PROVIDE CURRENT FLORIDA
 PRODUCT APPROVAL FL10124-R19.
  
 E) GARAGE OVERHEAD DOOR. NOA 11-0414.12 SUBMITTED WITH
 FLORIDA PRODUCT APPROVAL FL15371-R2 EXPIRED ON JULY 21,
 2015. NEED CURRENT NOA. NOTE: COORDINATE WITH THE
 REVISED DESIGN PRESSURES REQUIRED ON ITEM #4 ABOVE.
  
 F) CLARIFY WHY SUBMITTING PRODUCT APPROVAL FOR WINDOW
 MULLIONS. THERE ARE NOT WINDOW MULLIONS SPECIFIED ON
 PLANS. IN ADDITION, FLORIDA PRODUCT APPROVAL FL15353-R2
 SUBMITTED HAS A "PENDING FBC APPROVAL" STATUS.
  
 G) FIXED WINDOWS. FLORIDA PRODUCT APPROVAL FL15349-R5
 SUBMITTED WAS REVISED. NEED TO PROVIDE CURRENT FLORIDA
 PRODUCT APPROVAL FL15349-R8. NOTE: COORDINATE WITH THE
 REVISED DESIGN PRESSURES REQUIRED ON ITEM #4 ABOVE.
  
 H) SINGLE HUNG WINDOWS. FLORIDA PRODUCT APPROVAL
 FL17499 SUBMITTED WAS REVISED. NEED TO PROVIDE CURRENT
 FLORIDA PRODUCT APPROVAL FL17499-R1. NOTE: COORDINATE
 WITH THE REVISED DESIGN PRESSURES REQUIRED ON ITEM #4
 ABOVE.
  
 14- ENGINEER OF RECORD TO REVIEW/APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWIINGS FOR REFERENCE.
  