| Plan Review Notes For Permit 17010976 |
| Permit Number |
17010976 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-17 15:26:05 | PLAN REVIEW FAILED | | | | | | 1) NEED FAULT CURRENT CALCULATION FOR THE SERVICE PER | | | 110.24 (A,B) | | | 2) MAIN CIRCUIT BREAKER IS RATED AT 130 AMPERES? NOT A | | | STANDARD SIZE 240.6 | | | 3) CIRCUIT 11,15,17,19, AS SHOWN SHALL BE GFCI | | | PROTECTED 210.8 | | | 4) CIRCUIT #18 SHOWS 3 - 3WAY SWITCHES, NEEDS TO BE 2 - | | | 3WAYS AND A 4 WAY | | | 5) PANEL IN STORAGE ROOM NEEDS AT LEAST 36" OF FRONTAL | | | CLEARANCE 110.26 | | | 6) NO EXIT OR EMERGENCY LIGHTS SHOWN ON DRAWINGS | | | | | | JAKE LEAHY 561-805-6713 |
|