| Plan Review Notes For Permit 17010950 |
| Permit Number |
17010950 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-01-27 06:56:40 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 17010950 | | | ADD: 135 COSTELLO RD. | | | CONT: STARPRO ROOFING | | | TEL: 772-286-8308 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | | FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: FRI. JAN. 27/2017 | | | ACTION: DENIED | | | | | | 1) THE SUBMITTED ROOFING PERMIT WITH FLORIDA APPROVAL # | | | FL2984-R11INDICATED THE USE OF SUB-SYSTEM W-4 FROM | | | TABLE 1B-1 WOOD DECKS. SUB-SYSTEM W-4 IS FOR NEW OR | | | REROOF AND IS A MECHANICALLY ATTACHED ANCHOR SHEET, | | | BONDED INSULATION, BONDED ROOF COVER SHEET. THE | | | SUB-SYSTEM INDICATES IT IS GOOD FOR -60 PSF AND IN THE | | | LIMITATION SHEET 5 OF 6 UNDER THE NOTE 5.7 ENHANCED | | | FASTENING FOR ZONES 2 & 3 BY A FLORIDA DESIGN | | | PROFESSIONAL WILL BE REQUIRED. | | | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|